| 2002-04-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1) FBC-2001 SEC 424.2.6.1 ENGINEERING | | | DESIGN, CONSTRUCTION AND WORKMANSHIP. | | | ANSI/NSPI-4 92. NOTE #12 SHALL READ AS | | | STATED ABOVE. | | | 2) | | | FBC-2001 SEC 424.2.7.1 POOL CIRCULATING | | | PUMPS SHALL BE EQUIPPED ON THE INLET | | | SIDE WITH AN APPROVED TYPE HAIR AND LINT | | | STRAINER WHEN USED WITH A PRESSURE FIL- | | | TER. (DETAIL) | | | 3) | | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | | ORD. #2853-95, BACKFLOW REQUIRED ON | | | WATER SERVICE. (ADD TO NOTES) | | | 4) | | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|