2002-04-17 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT SOME
 ADDITIONAL LOADS ARE BEING ADDED AND ITS
 NOT REAL CLEAR FOR CIRCUTING.
 PLEASE SHOW BRANCH CIRCUITING ON PLANS
 AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE FOR ALL NEW CIRCUITS/ITEMS.
  
 2)NOTE: PLEASE SEE ANY FIRE REVIEW
 COMMENTS THAT MAY CHANGE ELECTRICAL
 PLANS.
  
 3)NOTE: PLEASE PROVIDE LOAD CALCS FOR
 EXISTING PANELS THAT NEW LOADS ARE BEING
 TIED INTO.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  