2002-04-24 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031422
 901 S FLAGLER DR / DINING FACILITY
  
 "PLAN RE3VIEW"
 ARCH: STEVEN KNIGHT
 TEL: (561)471-9370
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET A-0.1 CODES WRONG CODE ADDI-
 TION FOR THE ACCESSIBILITY & ENERGY,
 2001 FL BLD CODE:
 CHAPTER 11/ ACCESSIBILITY
 CHAPTER 13/ ENERGY
  
 2) DESIGN PARAMETERS: 2001 FL CODE IS
 ASCE 7/98, FIG 1606 (5) WIND SPEEDS
  
 IMPORTANCE FACTOR TO BE 1.15 TABLE 1606
 BUILDINGS OR STRUCTURES WHERE OCC LOAD
 IS 300 OR MORE IN ANY ONE ROOM.
  
 MISSING OTHER DESIGN INFO REQUIRED ON
 PLANS 1606.1.7.FL BLD CODE.
 WIND EXPOSURE;
 INTERNAL PRESSURE COEF
  
 3) FL BLD CODE 104.2.1.2 ADD INFO
 REQUIRED: TABLE 500 AS TO MINIMUM BLDG
 TYPE? SPRINKLERED/ NONSPRINKLER?
 THE STUDENT CENTER8,794SQ FT
 DINING AREA10,019SQ FT
 ADDITION 1,800SQ FT
 TOTAL20,613SQ FT
  
 DEPENDING ON THE TYPE CONST A SERVEY MAY
 BE REQUIRED IF AREA INCREASES ARE
 NECESSARY.
  
 4) FL ST STATUTE 553.71(7)
 "THRESHOLD BUILDING" MEANS ANY BUILDING
 WHICH IS GREATER THAN 3 STORIES OR 50'
 IN HEIGTH, OR WHICH HAS AN OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FL BLD
 CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS. INDICATE SQ FT BREAKDOWN
 AND OCCUPANT CONTENT.
  
 IF THIS MEETS THE CRITERIA FOR THRESHOLD
 BUILDING SUBMIT A THRESHOLD INSPECTION
 PLAN AND SPECIAL INSPECTOR TO REGISTER
 WITH DON NEELY.
  
 5) SITE SPECIFIC ENGINEERING (PRODUCT
 APPROVAL) REQUIRES THE WET SIGNATURE,
 DATE AND EMBOSSED SEAL OF THE ENGINEER
 CERTIFYING THE PRODUCT AND OF THE DESIGN
 PROFESSIONAL OF RECORD. FOR THE REUSE OF
 EXISTING GLAZING.
  
 6)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 STORM SHUTTERS, IF EUSED SITE SPECIFIC
 ENGINEERING AND INDICATE THE LARGE
 MISSLE TESTING FOR SHUTTERS.
  
 7)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, PROVIDE
 A SEATING PLAN AND EGRESSLAYOUT.
  
 THE DETAIL #3 OF A-1.3 INDICATES (2)
 4X4X1/4 STEEL ANGLE TO TIE IN THE STORE
 FRONT FRAME, NO INFORMATION AS HOW THIS
 WILL BE ANCHORED, DETAIL INDICATES 4"
 METAL STUD FRAMING, STRUCTURAL? NO INFO
 AS TO HOW TO FASTEN TOP PLATE?
 SAME DETAIL INDICATES A WOOD FRAMING MEM
 BER? FIRE TREATED, LOCATED IN A FIRE DIS
 TRICT AND BUILD TYPE NOT SPECIFIED?
  
 8) SAME DETAIL GIVES NO ANCHORING OR
 FASTENING, FL BLD CODE 1606.1.3 STRUCTUR
 AL MEMBERS AND SYSTEMS, AND COMPONENTS
 & CLADDING IN A BUILDING OR STRUCTURE
 SHALL BE ANCHORED TO RESIST WIND- INCLUD
 ING OVERTURNING, UPLIFT AND SLIDING.
  
 ANY QUESTIONS PLEASE CALL,
 JIM WITMER
 BUILDING PLAN REVIEW
 DEPARTMENT OF CONSTRUCTION SERVICES
 CITY OF WEST PALM BEACH
 (561) 659-8096 EXT. 8412