2002-03-22 00:00:00*****************UNSAT!*****************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUMBIT FOR REVIEW:
  
 1} A.I.C. RATING TO THE MAIN DISCONNECT.
  
 2} FEEDERS TO 60 AMP SUB PANEL TO COMPLY
 WITH 210-5 NEC & 215-8 CWPB
 AMMENDMENTS.
  
 3} INDICATE CONDUIT SIZE YO SUB PANEL.
  
 4} INDICATE LOCATION OF SERVICE
 EQUIPMENT.
  
 5} THE JOB VALUATION ON THE PERMIT
 APPLICATION DOESN'T SEEM CORRECT.
 PLEASE COMPLY WITH 104.6.5 CWPB
 AMMENDMENTS (ATTACHED).
  
 6} NOTE CODE ARTICLES 210-12 &
 210-11(C)(3).
  
  
 IF THERE ARE ANY QUESTIONS,PLEASE CALL:
  