| Plan Review Notes For Permit 02031384 |
| Permit Number |
02031384 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-22 00:00:00 | *****************UNSAT!***************** | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUMBIT FOR REVIEW: | | | | | | 1} A.I.C. RATING TO THE MAIN DISCONNECT. | | | | | | 2} FEEDERS TO 60 AMP SUB PANEL TO COMPLY | | | WITH 210-5 NEC & 215-8 CWPB | | | AMMENDMENTS. | | | | | | 3} INDICATE CONDUIT SIZE YO SUB PANEL. | | | | | | 4} INDICATE LOCATION OF SERVICE | | | EQUIPMENT. | | | | | | 5} THE JOB VALUATION ON THE PERMIT | | | APPLICATION DOESN'T SEEM CORRECT. | | | PLEASE COMPLY WITH 104.6.5 CWPB | | | AMMENDMENTS (ATTACHED). | | | | | | 6} NOTE CODE ARTICLES 210-12 & | | | 210-11(C)(3). | | | | | | | | | IF THERE ARE ANY QUESTIONS,PLEASE CALL: | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|