| Date |
Text |
| 2002-04-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHT M4.1 CONDENSATE SHALL NOT DRAIN | | | INTO SANITARY. CONDENSATE SHALL DRAIN | | | INTO A CONDENSATE LINE AND RUN SEPARATE | | | OUTSIDE OF BLDG. CONDENSATE SHALL HAVE | | | A RELIEF VENT AS THE LINE EXITS THE BLDG | | | AND TIE INTO A CATCH BASIN, STORM DRAIN, | | | OR DRYWELL IF APPROVED BY MECHANICAL | | | CODE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|