| Plan Review Notes For Permit 02031379 |
| Permit Number |
02031379 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-12 00:00:00 | A) GENERAL NOTES SECTION ON PAGE A1.1 | | | AND TITLE PAGE INDICATES EXITS TO COMPLY | | | WITH CHAPTER 5 OF THE LIFE SAFETY CODE. | | | THIS SHOULD READ CHAPTER 7 OF THE | | | LIFE SAFETY CODE SINCE THE 2000 EDITION | | | OF THE LIFE SAFETY CODE IS IN EFFECT. | | | B) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE ALARM SYSTEM REMODEL. | | | C) FIRE ALARM NOTES # 19 INDICATES FIRE | | | ALARM CIRCUITS WILL BE CLASS B, STYLE C. | | | ONLY CLASS A, STYLE D CIRCUITS WILL | | | BE PERMITTED. | | | D) PLEASE INDICATE RATINGS OF TENANT | | | SPACE DOORS LEADING FROM THE SPACE TO | | | CORRIDOR 312. | | | E) NO FIRE SPRINKLER PLANS PROVIDED. THE | | | FIRE SPRINKLER NOTES ARE INCORRECT. | | | REFERENCES ARE MADE REGARDING THE SOUTH | | | FLORIDA BUILDING CODE AND BROWARD | | | COUNTY EDITION. THE FIRE SPRINKLER | | | SYSTEM DESIGN IS TO COMPLY WITH NFPA 13, | | | 1999 EDITION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|