Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-04-12 00:00:00A) GENERAL NOTES SECTION ON PAGE A1.1
 AND TITLE PAGE INDICATES EXITS TO COMPLY
 WITH CHAPTER 5 OF THE LIFE SAFETY CODE.
 THIS SHOULD READ CHAPTER 7 OF THE
 LIFE SAFETY CODE SINCE THE 2000 EDITION
 OF THE LIFE SAFETY CODE IS IN EFFECT.
 B) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM REMODEL.
 C) FIRE ALARM NOTES # 19 INDICATES FIRE
 ALARM CIRCUITS WILL BE CLASS B, STYLE C.
 ONLY CLASS A, STYLE D CIRCUITS WILL
 BE PERMITTED.
 D) PLEASE INDICATE RATINGS OF TENANT
 SPACE DOORS LEADING FROM THE SPACE TO
 CORRIDOR 312.
 E) NO FIRE SPRINKLER PLANS PROVIDED. THE
 FIRE SPRINKLER NOTES ARE INCORRECT.
 REFERENCES ARE MADE REGARDING THE SOUTH
 FLORIDA BUILDING CODE AND BROWARD
 COUNTY EDITION. THE FIRE SPRINKLER
 SYSTEM DESIGN IS TO COMPLY WITH NFPA 13,
 1999 EDITION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910