Plan Review Notes
Plan Review Notes For Permit 02031379
Permit Number 02031379
Review Stop B
Sequence Number 1
Notes
Date Text
2002-04-23 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02031379
 326 FERN ST/ 3RD FL
 CONT: INTEC CONST
 TEL: 649-1115
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- COVER SHEET, CODE RESEARCH INDICATES
 1997 STANDARD BUILING CODE, SSHOULD READ
 2001 FLORIDA BUILDING CODE
  
 2)- COVER SHEET,GENERAL NOTES INDICATES
 THE 1994 FLORIDA ACCESSIBILITY CODE, THE
 FL ACCESSIBILITY CODE IS NOW CHAPTER11
 OF THE 2001 FL BLD CODE.
  
 3)- FL BLD CODE 903.8. MISSING FIRE
 SPRINKLER DRAWINGS.
  
 4)- OCCUPANT LOAD= 57 PEOPLE TABLE1003.1
  
 5)- FL BLD CODE 1012.1.2 EGRESS DOORS
 SHALL BE SIDE SWINGINGIN THE DIRECTION
 OF EGRESS WHEN SERVING AN OCCUPANT LOAD
 OF 50 OR MORE.
  
 6)- FL BLD CODE 1012.4 EGRESS DOORS DUR-
 ING ITS SWING SHALL LEAVE UNOBSTRUCTED
 AT LEAST ONE HALF THE REQUIRED WIDTH OF
 THE CORRIDOR, (22"). AT COLUMN LINE "E"
 THE DIMENSION IS NOT GIVEN, VERIFY!
  
 7)- THE 2 DOORS GAINING EGRESS INTO THE
 TENANT SPACE DO NOT GIVE THE RATING OF
 THE DOOR, FRAME OR CLOSER?
  
 8)- PROVIDE A FLOOR PLAN OF THE FURNI-
 TURE LAYOUT, INDICATE ACCESS CORRIDORS
  
 9)- DETAIL 8 OF 3.1 INDICATES A CUT
 SECTION OF A SOFFIT? WHERE IS IT TO BE
 USED? GIVE INFORMATION AS TO FASTENING
 SCHEDULE? TYPE OF FASTENER, FREQUENCY
 ETC? SPACING OF STUDS?
  
 10)- FL BLD CODE 1511.7 MECHANICAL UNITS
 ON THE ROOF, SEE TABLE 1511.7 CLEARENCES
 BELOW ROOF MOUNTED MECHANICAL UNITS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561) 659-8096 X 8412