| Plan Review Notes For Permit 02031324 |
| Permit Number |
02031324 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-08 00:00:00 | ****************DENIED****************** | | | | | | ADDITIONAL INFORMATION REQUIRED | | | 1. PROVIDE CFM REQUIREMENTS FOR DRYER TO | | | DETERMINE COMPLIANCE PER 2001 FBC(M) | | | 504.5 | | | 2. PROVIDE OUTSIDE AIR PER FBC(M) TABLE | | | 403.3 | | | 3. SEER ON EQUIPMENT SCHEDULE DOES NOT | | | MATCH SEER ON ENERGY CALCS | | | | | | NOTE: DRYER AND BATH EXHAUST DUCTS | | | SHALL NOT PENETRATE RATED PARTYWALL OR | | | ADJACENT ROOF |
|