Plan Review Notes
Plan Review Notes For Permit 02031318
Permit Number 02031318
Review Stop M
Sequence Number 2
Notes
Date Text
2002-05-09 00:00:00***********DENIED***********************
 1. SEER ON ENERGY CALCS STILL DO NOT
 MATCH SEER ON EQUIPMENT SCHEDULE
 2. OUTSIDE AIR CALCULATIONS SHALL
 PROVIDE COMPLIANCE WITH 402.2 (4% OF
 THE FLOOR AREA BEING VENTILATED) OR
 TABLE 403.3 (MECHANICAL VENTILATION NOT
 INFILTRATION)
 3. DRYER CFM NOT PROVIDED
 4. DRYER LEGTH'S IN EXCESS OF CODE
 MINIMUM 25" PER 504.6 SHALL HAVE
 MANUFACTURES SPEC'S INCLUDED FOR REVIEW
 SHOWING SPECIFIC'S OF ALLOWABLE LENGTH
 OF DUCT.
 5. SECONDARY DRAIN CONSPICUOUS POINT
 SHALL NOT BE BEHIND AHU CLOSET DOOR. IF
 NO SUITABLE CONSPICUOUS LOCATION IS
 AVAILABLE, A PAN WITH A FLOAT SWITCH
 PER 307.2.4 IS ACCEPTABLE.