| Plan Review Notes For Permit 02031318 |
| Permit Number |
02031318 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-05-09 00:00:00 | ***********DENIED*********************** | | | 1. SEER ON ENERGY CALCS STILL DO NOT | | | MATCH SEER ON EQUIPMENT SCHEDULE | | | 2. OUTSIDE AIR CALCULATIONS SHALL | | | PROVIDE COMPLIANCE WITH 402.2 (4% OF | | | THE FLOOR AREA BEING VENTILATED) OR | | | TABLE 403.3 (MECHANICAL VENTILATION NOT | | | INFILTRATION) | | | 3. DRYER CFM NOT PROVIDED | | | 4. DRYER LEGTH'S IN EXCESS OF CODE | | | MINIMUM 25" PER 504.6 SHALL HAVE | | | MANUFACTURES SPEC'S INCLUDED FOR REVIEW | | | SHOWING SPECIFIC'S OF ALLOWABLE LENGTH | | | OF DUCT. | | | 5. SECONDARY DRAIN CONSPICUOUS POINT | | | SHALL NOT BE BEHIND AHU CLOSET DOOR. IF | | | NO SUITABLE CONSPICUOUS LOCATION IS | | | AVAILABLE, A PAN WITH A FLOAT SWITCH | | | PER 307.2.4 IS ACCEPTABLE. |
|