| Date |
Text |
| 2002-05-14 00:00:00 | CHECKLIST: |
| | 1-DRAWINGS THAT WERE REVISED WERE NOT |
| | SEALED AS REQUIRED BY CHAPTER 481 |
| | FLORIDA STATUTES. |
| | 2-MODEL C1 DOESN'T COMPLY WITH TABLE 600 |
| | FBC 2001 WHEN HAVING THE OPTION OF |
| | SLIDING GLASS DOORS AT MORNING ROOM |
| | INSTEAD OF SINGLE HUNG WINDOW. |
| | NOTE: THIS COMMENT WAS ADDRESSED |
| | DURING PRELIMINARY REVIEWS DONE AT THE |
| | EARLY STAGE OF CONSTRUCTION OF THESE |
| | TOWNHOUSES. |
| | 3-THERE ARE SOME PAGES THAT NEED TO BE |
| | UPDATED USING THE FBC 2001. EG: SEE |
| | FIREPLACE OPTIONS AND TWO STORY MODEL |
| | DETAILS. |
| | 4-REVISE BUCK DETAIL SHOWING HOW DOES IT |
| | COMPLY WITH SECTION 1704.4.4.2 FBC |
| | 2001. DON'T CITE THE SECTION. SEE |
| | SECTION FOR FULL SIZE OF BUCK. |
| | 5-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ROOF TILE. PRODUCT APPROVAL SUBMITTED |
| | IS NOT GOOD BECAUSE IT WAS DELETED |
| | FROM THE SBCCI LISTING. |
| | B)HORIZONTAL SLIDERS WINDOWS. |
| | C)FIREPLACE UL LISTING & SPECS & DETAILS |
| | D)GARAGE DOORS: ONLY DADE COUNTY PRODUCT |
| | APPROVALS MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ARCHITECT. SBCCI |
| | PRODUCT APPROVAL DOESN'T. SUBMIT ONLY |
| | DADE COUNTY PRODUCT APPROVALS TO AVOID |
| | CONFUSION AND CONFLICTS. |
| | 6-APPLY FOR SCREEN ENCLOSURES UNDER |
| | SEPARATE PERMITS. |
| | |
| | NOTES: |
| | *DRAWINGS AND COMMENTS TO BE FILED UNDER |
| | PERMIT #02031318. |
| | *THESE COMMENTS APPLY TO PERMIT NUMBERS: |
| | 02031318, 02031320, 02031322 AND |
| | 02031324. |