2002-04-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FHA AMEND 98 DESIGN 24 CFR
 100.205(C)(2)-(3) DESIGN MAN-
 UAL.
  
 1) SHT SH-1 GENERAL NOTES #6 TO READ
 FBC-2001 PLUMBING.
 2) SHT BR_MP-1 WATER RISER DIAGRAM,
 A WATER HAMMER ARRESTOR SHALL BE IN-
 STALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (WASH MACHINES - DISH WASHERS
 AND ICE MAKERS) FBC-2001 SEC 604.9
 ALSO REMOVE THE AIR CHAMBER AT W/HEATER
 3) SHT B_MP-4 FOR ALL B & BR UNITS.
 THE RELIEF VALVE DISCHARGE PIPE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. FBC-2001 SEC 504.7.1
 4) SHT B_MP-4 GENERAL NOTES AND SPECS.
 GEN NOTE # 1(B) TO READ FBC-2001 PLUMB.
 5) SHT C1_MP-1 WATER RISER DIAGRAM,
 A WATER HAMMER ARRESTOR SHALL BE IN-
 STALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (WASH MACHINES - DISH WASHERS
 AND ICE MAKERS) FBC-2001 SEC 604.9
 6) SHT C_MP-4 WATER HEATER DETAIL,
 THE RELIEF VALVE DISCHARGE PIPE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. FBC-2001 SEC 504.7.1
 7) SHT C_MP-4 PLUMBING GENERAL NOTES &
 8) SHT A1_MP-1 SANITARY RISER DIAGRAM,
 OPTIONAL LAUNDRY SINK SHALL BE TAKEN OFF
 TO THE RIGHT OF THE BLDG DRAIN AWAY FROM
 THE WASH MACHINE TO REFLECT FLOOR PLAN.
 8) SHT A1_MP-1 WATER RISER DIAGRAM,
 A WATER HAMMER ARRESTOR SHALL BE IN-
 STALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (WASH MACHINES - DISH WASHERS
 AND ICE MAKERS) FBC-2001 SEC 604.9
 9) SHT A_MP-3 WATER HEATER DETAIL,
 THE RELIEF VALVE DISCHARGE PIPE
 SHALL NOT HAVE ANY TRAPPED SECTIONS AND
 SHALL HAVE A VISIBLE AIR GAP OR AIR GAP
 FITTING LOCATED IN THE SAME ROOM AS THE
 WATER HEATER. FBC-2001 SEC 504.7.1
 10) SHT A_MP-3 PLUMBING GENERAL NOTES &
 SPECS., NOTE #1(B) TO READ FBC-2001 PLMG
 11) SHT B_MP-1 WATER RISER DIAGRAM,
 A WATER HAMMER ARRESTOR SHALL BE IN-
 STALLED WHERE QUICK CLOSING VALVES ARE
 UTILIZED. (WASH MACHINES - DISH WASHERS
 AND ICE MAKERS) FBC-2001 SEC 604.9
  
 REVIEW BY KEN STEVENS