| 2002-04-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FHA AMEND 98 DESIGN 24 CFR |
| | 100.205(C)(2)-(3) DESIGN MAN- |
| | UAL. |
| | |
| | 1) SHT SH-1 GENERAL NOTES #6 TO READ |
| | FBC-2001 PLUMBING. |
| | 2) SHT BR_MP-1 WATER RISER DIAGRAM, |
| | A WATER HAMMER ARRESTOR SHALL BE IN- |
| | STALLED WHERE QUICK CLOSING VALVES ARE |
| | UTILIZED. (WASH MACHINES - DISH WASHERS |
| | AND ICE MAKERS) FBC-2001 SEC 604.9 |
| | ALSO REMOVE THE AIR CHAMBER AT W/HEATER |
| | 3) SHT B_MP-4 FOR ALL B & BR UNITS. |
| | THE RELIEF VALVE DISCHARGE PIPE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE |
| | WATER HEATER. FBC-2001 SEC 504.7.1 |
| | 4) SHT B_MP-4 GENERAL NOTES AND SPECS. |
| | GEN NOTE # 1(B) TO READ FBC-2001 PLUMB. |
| | 5) SHT C1_MP-1 WATER RISER DIAGRAM, |
| | A WATER HAMMER ARRESTOR SHALL BE IN- |
| | STALLED WHERE QUICK CLOSING VALVES ARE |
| | UTILIZED. (WASH MACHINES - DISH WASHERS |
| | AND ICE MAKERS) FBC-2001 SEC 604.9 |
| | 6) SHT C_MP-4 WATER HEATER DETAIL, |
| | THE RELIEF VALVE DISCHARGE PIPE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE |
| | WATER HEATER. FBC-2001 SEC 504.7.1 |
| | 7) SHT C_MP-4 PLUMBING GENERAL NOTES & |
| | 8) SHT A1_MP-1 SANITARY RISER DIAGRAM, |
| | OPTIONAL LAUNDRY SINK SHALL BE TAKEN OFF |
| | TO THE RIGHT OF THE BLDG DRAIN AWAY FROM |
| | THE WASH MACHINE TO REFLECT FLOOR PLAN. |
| | 8) SHT A1_MP-1 WATER RISER DIAGRAM, |
| | A WATER HAMMER ARRESTOR SHALL BE IN- |
| | STALLED WHERE QUICK CLOSING VALVES ARE |
| | UTILIZED. (WASH MACHINES - DISH WASHERS |
| | AND ICE MAKERS) FBC-2001 SEC 604.9 |
| | 9) SHT A_MP-3 WATER HEATER DETAIL, |
| | THE RELIEF VALVE DISCHARGE PIPE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE |
| | WATER HEATER. FBC-2001 SEC 504.7.1 |
| | 10) SHT A_MP-3 PLUMBING GENERAL NOTES & |
| | SPECS., NOTE #1(B) TO READ FBC-2001 PLMG |
| | 11) SHT B_MP-1 WATER RISER DIAGRAM, |
| | A WATER HAMMER ARRESTOR SHALL BE IN- |
| | STALLED WHERE QUICK CLOSING VALVES ARE |
| | UTILIZED. (WASH MACHINES - DISH WASHERS |
| | AND ICE MAKERS) FBC-2001 SEC 604.9 |
| | |
| | REVIEW BY KEN STEVENS |