| 2002-04-22 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT# 02031318 |
| | 2169 BIG WOOD CAY |
| | CONT: TOWN & COUNTRY |
| | TEL: (561)893-0029 |
| | |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1)- DESIGN CRITERIA : FBC 2001 SECTION |
| | 1606.2 SHALL NOT BE USED TO DESIGN A |
| | "PARTIALLY ENCLOSED" BLDG. SEE SECTION |
| | 1606.1.4.1 FL BLD CODE |
| | |
| | 2)- THE 2-HR OVERHANG DETAIL FOR THE |
| | WOOD ASSEMBLY USING THE CALCULATED RAT- |
| | ING IS NOT ACCEPTABLE , SEC 709.6.1.2 |
| | USE THE UL RATING OR GYP ASS NUMBER. |
| | |
| | 3)- REVISE STRUCTURAL BUCK DETAIL TO SAT |
| | ISFY REQUIREMENTS OF SEC 1707.4.4. |
| | |
| | 4)- PROVIDE CEILING ATTACHMENT OF FRONT |
| | & BACK PORCH, SEE ASTM C1063 FOR HI-RIB |
| | IN HORIZONTAL FRAMING MEMBERS |
| | |
| | 5)- REVISE ENERGY CALC: UNDER ATTIC AREA |
| | SEE FL BLD CODE CHAPTER 6 604.1.ABC.1 |
| | |
| | 6)- PROVIDE PRODUCT APPROVAL FOR ROOF |
| | TILE, REPORT SUBMITTED DELETED FROM |
| | SBCCI LISTING. |
| | |
| | 7)- SHEET C-A-3 OPTIONS THE "X" DELETION |
| | DOES NOT LINE UP WITH OPTIONS |
| | |
| | 8)- SHEET S1.1 MISSING INFO FL BLD CODE |
| | 1909.3(2) CONCRETE SLABS ON GROUND CON- |
| | TAINING 6X6 W1.4XW1.4 WELDED WIRE REIN- |
| | FORCEMENT FABRIC LOCATED IN THE MIDDLE |
| | TO UPPER 1/3RD OF THE SLAB ARE TO HAVE |
| | APPROVED MATERIALS OR SUPPORTS AT SPAC- |
| | ING NOT TO EXCEED 3 FT OR IN ACCORDANCE |
| | WITH THE MANUFACTURERS SPEC |
| | |
| | 9)- STRUCTURAL SHEETS SPECIFY "HUGHES" |
| | NO LONGER IN BUSINESS, SPEC OUT THE |
| | CURRENT DEVISES CURRENTLY BEING USED! |
| | |
| | 10)- S-5 DETAILS 2 & 11 MISSING FIRE |
| | BLOCKING |
| | |
| | 11)- FLOOD ZONE A-0 ELEVATION CERTIFI- |
| | CATE REQUIRED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096X8412 |