2002-04-22 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02031318
 2169 BIG WOOD CAY
 CONT: TOWN & COUNTRY
 TEL: (561)893-0029
  
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1)- DESIGN CRITERIA : FBC 2001 SECTION
 1606.2 SHALL NOT BE USED TO DESIGN A
 "PARTIALLY ENCLOSED" BLDG. SEE SECTION
 1606.1.4.1 FL BLD CODE
  
 2)- THE 2-HR OVERHANG DETAIL FOR THE
 WOOD ASSEMBLY USING THE CALCULATED RAT-
 ING IS NOT ACCEPTABLE , SEC 709.6.1.2
 USE THE UL RATING OR GYP ASS NUMBER.
  
 3)- REVISE STRUCTURAL BUCK DETAIL TO SAT
 ISFY REQUIREMENTS OF SEC 1707.4.4.
  
 4)- PROVIDE CEILING ATTACHMENT OF FRONT
 & BACK PORCH, SEE ASTM C1063 FOR HI-RIB
 IN HORIZONTAL FRAMING MEMBERS
  
 5)- REVISE ENERGY CALC: UNDER ATTIC AREA
 SEE FL BLD CODE CHAPTER 6 604.1.ABC.1
  
 6)- PROVIDE PRODUCT APPROVAL FOR ROOF
 TILE, REPORT SUBMITTED DELETED FROM
 SBCCI LISTING.
  
 7)- SHEET C-A-3 OPTIONS THE "X" DELETION
 DOES NOT LINE UP WITH OPTIONS
  
 8)- SHEET S1.1 MISSING INFO FL BLD CODE
 1909.3(2) CONCRETE SLABS ON GROUND CON-
 TAINING 6X6 W1.4XW1.4 WELDED WIRE REIN-
 FORCEMENT FABRIC LOCATED IN THE MIDDLE
 TO UPPER 1/3RD OF THE SLAB ARE TO HAVE
 APPROVED MATERIALS OR SUPPORTS AT SPAC-
 ING NOT TO EXCEED 3 FT OR IN ACCORDANCE
 WITH THE MANUFACTURERS SPEC
  
 9)- STRUCTURAL SHEETS SPECIFY "HUGHES"
 NO LONGER IN BUSINESS, SPEC OUT THE
 CURRENT DEVISES CURRENTLY BEING USED!
  
 10)- S-5 DETAILS 2 & 11 MISSING FIRE
 BLOCKING
  
 11)- FLOOD ZONE A-0 ELEVATION CERTIFI-
 CATE REQUIRED.