| Plan Review Notes For Permit 02031316 |
| Permit Number |
02031316 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-28 00:00:00 | *******************DENIED*************** | | | | | | | | | 1.AIR EXHAUSTED FROM SPRAY OPERATIONS | | | SHALL BE CONDUCTED BY DUCTS DIRECTLY | | | TO THE OUTSIDE OF THE BUILDING. | | | EXHAUST DUCTS SHALL FOLLOW THE MOST | | | DIRECT ROUTE TO THE POINT OF DIS- | | | CHARGE, BUT SHALL NOT PENETRATE A | | | FIRE WALL. | | | | | | 2.EXHAUST DISCHARGE SHALL BE DIRECTED | | | AWAY FROM ANY FRESH AIR INTAKES AND | | | A MINIMUM OF 6 FT FROM ANY EXTERIOR | | | WALL OR ROOF. | | | | | | 3.EXHAUST SHALL NOT BE LOCATED LESS | | | THAN 10 FT HORIZONTALLY FROM PARTS | | | OF THE SAME OR CONTIGUOUS BUILDINGS | | | AND ADJACENT PROPERTY LINE. | | | | | | SEE ALSO FIRE DEPT COMMENTS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|