| 2002-03-28 00:00:00 | A) IT WAS NOTED FROM THE PLANS THAT THE | | | SPRAY BOOTH IS LOCATED DIRECTLY NEXT | | | TO A WALL. THIS ARRANGEMENT CAN ONLY | | | BE ALLOWED IF THE ALL PARTS OF THE | | | SPRAY BOOTH CAN BE CLEANED. PLEASE | | | ADVISE. | | | B) PLEASE INDICATE HOW THE SPRAY BOOTH | | | IS TO BE GROUNDED AND BONDED TO PREVENT | | | STATIC ELECTRICITY. | | | C) PLEASE PROVIDE A FLOOR PLAN OF THE | | | SPACE WHERE THE SPRAY BOOTH IS PLANNED | | | AND PLEASE LOCATE EXIT DOOR LOCATIONS. | | | D) GLASS USED FOR THE LIGHT FIXTURES | | | MUST BE EITHER WIRED GLASS, HEAT | | | TREATED GLASS, OR HAMMERED WIRE GLASS. | | | E) NO PANELS PROVIDED IN EXHAUST DUCT | | | FOR INSPECTION OR CLEANING. | | | F) HOW IS THE FLAMMABLE OR COMBUSTIBLE | | | LIQUIDS PLANNED FOR USE TO BE STORED. | | | G) THE EXHAUST DUCT FOR THE BOOTH | | | TERMINATES ON THE SAME PROPERTY, ANY | | | RIGHT OF WAYS, OR SOMEONE ELSE'S | | | PROPERTY. PLEASE EXPLAIN. | | | H) ELECTRIC TO COMPLY WITH NFPA 33. | | | I) PLEASE PROVIDE DATA FOR FILTERS | | | PLANNED FOR USE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|