Plan Review Notes
Plan Review Notes For Permit 02031302
Permit Number 02031302
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-03-26 00:00:00A) WET FIRE HYDRANTS REQUIRED PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
 B) FIRE HYDRANTS ARE TO BE SPACED
 BETWEEN 300-500 FEET APART.
 C) CLEARANCES OF AT LEAST SEVEN FEET
 6 INCHES MUST BE PROVIDED TO THE FRONT
 AND SIDES OF EACH FIRE HYDRANT. AT
 LEAST FOUR FEET MUST BE PROVIDED TO THE
 REAR OF ALL FIRE HYDRANTS.
 D) NO ITEMS THAT WOULD OBSTRUCT THE
 USES OF THE FIRE HYDRANTS WILL BE
 ALLOWED.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910