| Plan Review Notes For Permit 02031269 |
| Permit Number |
02031269 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-29 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 02031269 | | | 7880 NILE RIVER ROAD | | | CONT: SCREEN ETC INC | | | TEL: 439-3619 | | | | | | FL BLDG CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1)- THE DESIGN PARAMETERS SHEET INDI- | | | CATES A BASIC VELOCITY PRESSURE OF 10BLS | | | TABLE 2002.4 DESIGN WIND PRESSURES FOR | | | ALUMINIUM SCREEN ENCLOSURE FRAMING. | | | THE TABLE FOR 140 MPH WIND SPEED INDICAT | | | ES FOR A FLAT ROOF A MINIMUM OF 10 PSF | | | TO BE USED. | | | WALLS L/W EXPOS "B" 16 PSF TO BE USED. | | | | | | 2) ELEVATION DETAIL DOESN'T INDICATE THE | | | MANSARD, IS THERE ANY EXT SCREEN DOOR? | | | | | | 3) DISCREPANCY BETWEEN DETAILS: | | | CARRY-BEAM TO BEAM CONNECTION, IN DETAIL | | | THREE BOLTS DRAWN AND THE WRITTEN EX- | | | PLINATION TWO BOLTS? | | | | | | 4)- FL BLDG CODE 2002.3.2 SCREEN DENSITY | | | SHALL BE A MAXIMUM OF 20X20 MESH. | | | | | | 5)- FL BLDG 2003.8.1.4 WELDER QUALIFICA- | | | TION ALL WELDING OF STRUCTURAL MEMBERS | | | SHALL BE PERFORMED BY CERTIFIED WELDERS. | | | | | | 6)- ENCIRLE ALL DETAILS TO BE USED, IF N | | | OT WELDED BOX BEAM SPLICE SHOULD BE | | | ENCIRCLED. | | | | | | 7)- ALL CONNECTION DEVISES SHALL BE | | | RATED BY LOAD TESTING LAB. 2003.7.5 | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561) 659-8096 X8412 |
|