| Plan Review Notes For Permit 02031234 |
| Permit Number |
02031234 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS - NFPA-58 | | | | | | 1) MORE INFORMATION REQUIRED. PLEASE | | | SUBMIT A PLAN TO SHOW ALL DOORS AND | | | WINDOWS. | | | | | | 2) PLEASE SUBMIT MANUFACTURE INFORMATION | | | FOR OVEN/RANGE. SHOW BTU'S AND SHOW | | | LISTING BY AN APPROVED AGENCY. | | | | | | 3) PLEASE SUBMIT MANUFACTURE INFORMATION | | | FOR REGULATOR. SHOW RANGE FOR REGULATOR | | | (INPUT - OUTPUT). | | | | | | 4)EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|