| Plan Review Notes For Permit 02031197 |
| Permit Number |
02031197 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-02 00:00:00 | **************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT A LOAD CALCULATION | | | SHOWING ALL NEW EQUIPMENT AND TO INCLUDE | | | ALL LIGHTING/REC CIRCUITS. 220-3,220-10, | | | 220-11,220-13. | | | PLEASE SHOW ALL CONTINUOUS LOADS AT 125% | | | 215-2,3/ 230-42. | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH A SUBMITTED PANEL | | | SCHEDULE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|