Plan Review Notes
Plan Review Notes For Permit 02031182
Permit Number 02031182
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-02 00:00:00***************** UNSAT ***************
  
 1)NOTE:PLEASE CLARIFY LOAD ON EXISTING
 SERVICE. SERVICE IS SHOWN AS 600A WITH
 A NEWLOAD OF 143AMPS BEING ADDED.
  
 2)NOTE: PLEASE NOTE THAT PANEL IS SHOWN
 AS BEING RATED FOR 150A`S WITH A 200A
 FEED. PLEASE CORRELATE.
  
 3)NOTE: PLEASE NOTE MISSING SHOW WINDOW
 OUTLET PER 210-62. PLEASE NOTE 12` OR
 PORTIONS OF WINDOWS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 EELCTRICAL PLAN REVIEW
 561-659-8096 EXT 8372