| Plan Review Notes For Permit 02031086 |
| Permit Number |
02031086 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-02 00:00:00 | *************DENIED******************* | | | 1. SEER ON EQUIPMENT SCHEDULE DOES NOT | | | MATCH SEER ON ENERGY CALCS | | | 2. PROVIDE CFM INFORMATION ON DRYER TO | | | DETERMINE COMPLIANCE WITH FBC(M) 504.5 | | | 3. PROVIDE OUTSIDE AIR PER 2001 FBC(M) | | | TABLE 403.3 | | | | | | NOTE: DRYER AND BATH EXHAUST DUCT SHALL | | | NOT PENETRATE RATED PARTYWALL OR | | | ADJACENT ROOF |
|