| Plan Review Notes For Permit 02031081 |
| Permit Number |
02031081 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-18 00:00:00 | NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | PLEASE INDICATE THE SIZE OF THE OVER | | | CURRENT PROTECTION FOR THE#3 FEEDERS | | | TO THE INDOOR PANEL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|