| Plan Review Notes For Permit 02031079 |
| Permit Number |
02031079 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-08-13 00:00:00 | 1) THE FIRE HYDRANTS SHOWN ON THE SITE | | | PLAN ARE LOCATED BEHIND A CHAIN-LINK | | | FENCE AND PROVIDES NO PROTECTION FOR | | | THE TOOL EQUIPMENT RENTAL. | | | | | | 2) NO DETAILS PROVIDED FOR THE PROPOSED | | | LP GAS TANK SHOWN ON THE SITE PLAN. NO | | | BARRIER PROTECTION SHOWN FOR THE LG | | | GAS TANK OR PROPOSED 3000 GALLON FUEL | | | TANK. SEPARATE PLANS AND PERMITS | | | REQUIRED. | | | | | | 3) GAS METER NOTED NEAR WELDING AREA. | | | | | | 4) PLEASE ENSURE THAT ELECTRICAL | | | DRAWINGS MATCH THE ARCHITECTURAL | | | DRAWINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|