Plan Review Notes
Plan Review Notes For Permit 02031079
Permit Number 02031079
Review Stop B
Sequence Number 3
Notes
Date Text
2002-08-21 00:00:00THE VARCO-PRUDEN PLANS ARE REFERENCED TO
 THE "IBC" CODE AND A 120 MPH WIND
 SPEED.
  
 A PORTION OF THE V-P CALCULATIONS
 IDENTIFIED AS "BUILDING 1" CITE 120 MPH.
  
 THE CITY IS UNDER THE 2001 FLORIDA
 BUILDING CODE, (FBC) AND WHOLLY WITHIN
 A 140MPH WIND ZONE.THE PLANS MUST
 REFLECT WIND DESIGN TO EITHER FBC 1606
 OR ASCE 7-98.PLEASE REVISE AS
 NECESSARY WITH THE ENGINEER OF RECORD
 HAVING REVIEWED THE V-P PLANS FOR
 CONFIRMATION WITH DESIGN INTENT.