| Plan Review Notes For Permit 02031079 |
| Permit Number |
02031079 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-08-21 00:00:00 | THE VARCO-PRUDEN PLANS ARE REFERENCED TO | | | THE "IBC" CODE AND A 120 MPH WIND | | | SPEED. | | | | | | A PORTION OF THE V-P CALCULATIONS | | | IDENTIFIED AS "BUILDING 1" CITE 120 MPH. | | | | | | THE CITY IS UNDER THE 2001 FLORIDA | | | BUILDING CODE, (FBC) AND WHOLLY WITHIN | | | A 140MPH WIND ZONE.THE PLANS MUST | | | REFLECT WIND DESIGN TO EITHER FBC 1606 | | | OR ASCE 7-98.PLEASE REVISE AS | | | NECESSARY WITH THE ENGINEER OF RECORD | | | HAVING REVIEWED THE V-P PLANS FOR | | | CONFIRMATION WITH DESIGN INTENT. |
|