| Date |
Text |
| 2002-04-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2002 PLUMBING - FACBC-97 |
| | FBC-2001 FUEL GAS - NFPA-58 |
| | |
| | 1) SHT A-1 PLEASE SUBMIT TOILET ROOM |
| | DETAILS. SHOW COMPLIANCE WITH FACBC SEC |
| | 4.16 AND SEC 4.19 AND ALL SUBSECTIONS. |
| | PLEASE SUBMIT IN A 1/8" OR 1/4" SCALE, |
| | SHOW W/C'S TO BE 1'6" OFF WALL TO CENTER |
| | 2) SHT A-1 PLEASE SHOW COMPLIANCE WITH |
| | FACBC SEC 4.15.2, AND SEC 4.1.3(10) FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 3) SHT P-1, WILL THE EYEWASH ALSO HAVE |
| | AN EMEMRGENCY SHOWER? |
| | 4) SHTS P-2/P-3 FUNNEL FLOOR DRAIN NOT |
| | APPROVED. ALL INDIRECT WASTE AND DRIPS |
| | SHALL DRAIN INTO A FLOOR SINK. 802.2 & |
| | 802.3 |
| | 5) SHT P-3 SANITARY RISER DIAGRAM, 2-WAY |
| | CLEAN OUTS ARE REQUIRED ON PIPES ENTER- |
| | ING AND EXITING THE GREASE TRAP. SEE |
| | ATTACHED SHEET FOR APPROVED GREASE TRAP |
| | DETAIL. |
| | 6) SHT P-3 GEN PLMG NOTES #1 NFPA 58 IS |
| | FOR L.P. GAS NOT NFPA 54. #3 SIZE TO BE |
| | BASED ON FBC-2001 FUEL GAS TABLE APPROI- |
| | ATE FOR LP AND INDICATED PRESSURE. |
| | 7) GREASE TRAP TO BE SIZED BY RODNEY |
| | COMPO ENVIRONMENTAL COMPLIANCE PER UTIL- |
| | ITY ORD #2938-96. PLEASE CALL (561)- |
| | 837-4074. |
| | 8) SHT P-4 WATER HEATER DETAIL, DIELECT- |
| | RIC UNIONS NOT APPROVED. |
| | 9) SEPARATE GAS PERMIT REQUIRED. FOLLOW- |
| | ING IS LIST OF GAS PERMIT APPLICATION |
| | REQUIREMENTS NEEDED FOR PERMIT. |
| | A. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 GAS CODE SEC. 402.4. |
| | B. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2001 FUEL GAG CODE |
| | 501.13 AND 501.14 |
| | C. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE CHAPTER 6. |
| | D. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | E. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | 10) SHT C1 INDICATES A LP GAS TANK IN |
| | THE S.W. CORNER, AND SHT P-2 SHOWS LP |
| | TANKS NEAR THE S.E END OF THE BLDG. |
| | PLEASE CLAIRFY. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |