Plan Review Notes
Plan Review Notes For Permit 02031079
Permit Number 02031079
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-04-03 00:00:00A) FIRE HYDRANTS ARE TO BE PROVIDED ON
 THE PROPERTY. NO FIRE HYDRANTS ARE
 SHOWN ON THE SITE PLAN.
 B) HOW DOES FIRE AND PARAMEDICAL
 EQUIPMENT ACCESS THE PROPERTY WHEN THE
 SLIDING GATES ARE CLOSED. WHAT
 PROVISIONS WILL BE MADE.
 C) BUILDING ADDRESS REQUIRED.
 D) MORE DETAILS REQUIRED ON LP GAS
 STORAGE AND AND ABOVE GROUND FUEL TANK
 SHOWN ON SITE PLAN.
 E) SEPARATE PLAN AND PERMITS REQUIRED
 ON SPRAY BOOTH AND EXTINGUISHING SYSTEM.
 F) PLEASE INDICATE WHAT BUILDING AND
 FIRE CODES THE BUILDING WAS DESIGNED
 TO.
 G) PLEASE INDICATE OCCUPANT LOADS FOR
 THE BUILDING.
 H) THE PAINT SPRAY BOOTH MUST HAVE AT
 LEAST THREE FEET ON ALL SIDES OF IT
 TO PROVIDE CLEANING CAPABILITIES.
 I) ARE ALL EXIT SIGNS SHOWN ON THE
 LIGHTING FLOOR PLAN.
 J) PLEASE PROVIDE MORE DETAILS ON WELDER
 50A.
 K) PLEASE INDICATE ALL FIRE EXTINGUISHER
 LOCATIONS.
 L) PLEASE EXPLAIN EXITING RATIONALE FROM
 DISPLAY AREA 101. IT APPEARS THAT
 EXITING ENTERS INTO A MORE HAZARDOUS
 AREA.
 M) THE PLANS INDICATE THAT THE BUILDING
 WILL BE CLASSIFIED AS BUSINESS. THE
 LIFE SAFETY CODE DEFINES BUSINESS AS
 "AS ONE USED FOR ACCOUNT AND RECORD
 KEEPING PURPOSES OR THE TRANSACTION
 OF BUSINESS OTHER THAN MERCANTILE" THIS
 OFFICE DOES NOT APPEAR TO BE CORRECTLY
 CATEGORIZED.
 N) PLEASE INDICATE USES FOR WAREHOUSE 1,
 PUMP AND POWER STORAGE, AND DISPLAY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910