| 2002-04-03 00:00:00 | A) FIRE HYDRANTS ARE TO BE PROVIDED ON |
| | THE PROPERTY. NO FIRE HYDRANTS ARE |
| | SHOWN ON THE SITE PLAN. |
| | B) HOW DOES FIRE AND PARAMEDICAL |
| | EQUIPMENT ACCESS THE PROPERTY WHEN THE |
| | SLIDING GATES ARE CLOSED. WHAT |
| | PROVISIONS WILL BE MADE. |
| | C) BUILDING ADDRESS REQUIRED. |
| | D) MORE DETAILS REQUIRED ON LP GAS |
| | STORAGE AND AND ABOVE GROUND FUEL TANK |
| | SHOWN ON SITE PLAN. |
| | E) SEPARATE PLAN AND PERMITS REQUIRED |
| | ON SPRAY BOOTH AND EXTINGUISHING SYSTEM. |
| | F) PLEASE INDICATE WHAT BUILDING AND |
| | FIRE CODES THE BUILDING WAS DESIGNED |
| | TO. |
| | G) PLEASE INDICATE OCCUPANT LOADS FOR |
| | THE BUILDING. |
| | H) THE PAINT SPRAY BOOTH MUST HAVE AT |
| | LEAST THREE FEET ON ALL SIDES OF IT |
| | TO PROVIDE CLEANING CAPABILITIES. |
| | I) ARE ALL EXIT SIGNS SHOWN ON THE |
| | LIGHTING FLOOR PLAN. |
| | J) PLEASE PROVIDE MORE DETAILS ON WELDER |
| | 50A. |
| | K) PLEASE INDICATE ALL FIRE EXTINGUISHER |
| | LOCATIONS. |
| | L) PLEASE EXPLAIN EXITING RATIONALE FROM |
| | DISPLAY AREA 101. IT APPEARS THAT |
| | EXITING ENTERS INTO A MORE HAZARDOUS |
| | AREA. |
| | M) THE PLANS INDICATE THAT THE BUILDING |
| | WILL BE CLASSIFIED AS BUSINESS. THE |
| | LIFE SAFETY CODE DEFINES BUSINESS AS |
| | "AS ONE USED FOR ACCOUNT AND RECORD |
| | KEEPING PURPOSES OR THE TRANSACTION |
| | OF BUSINESS OTHER THAN MERCANTILE" THIS |
| | OFFICE DOES NOT APPEAR TO BE CORRECTLY |
| | CATEGORIZED. |
| | N) PLEASE INDICATE USES FOR WAREHOUSE 1, |
| | PUMP AND POWER STORAGE, AND DISPLAY. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |