| Notes |
| Date |
Text |
| 2002-04-02 00:00:00 | ***********DENIED*********************** | | | | | | ADDITIONAL INFORMATION NEEDED: | | | 1.PROVIDE CFM REQUIREMENTS FOR DRYER TO | | | DETERMINE COMPLIANCE REQUIREMENTS PER | | | 2001 FBC(M) 504.5 | | | 2. PROVIDE OUTSIDE AIR PER SBC(M) TABLE | | | 403.3 | | | 3. SEER ON EQUIPMENT SCHEDULE DOES NOT | | | MATCH SEER ON ENERGY CALCS | | | | | | NOTE: DRYER AND BATH EXHAUST DUCTS SHALL | | | NOT PENETRATE RATED PARTYWALL OR | | | ADJACENT ROOF |
|