| 2002-05-15 00:00:00 | APPROVED WITH PROVISO: |
| | 1-TWO HOUR OVERHANG DETAIL FOR WOOD |
| | ASSEMBLY USING CALCULATED RATINGS IS |
| | NOT ALLOWED. SEE SECTION 709.6.1.2 |
| | FBC 2001. REVISE AS REQUIRED. |
| | 2-REVISE OR OMIT 2HR FIRE RATED GLASS |
| | BLOCK DETAIL. SEE UL ASSEMBLY SPECS |
| | FOR TWO HR FIRE RATED ASSEMBLY. |
| | 3-REVISE BUCK DETAILS. SEE SECTION |
| | 1704.4.2 FBC 2001 FOR SPECIFICATIONS |
| | REGARDING THE EXTEND OF THE BUCK. |
| | 4-PROVIDE COMPLETE SPECIFICATIONS FOR |
| | INSTALLATION OF CEILINGS AT FRONT AND |
| | REAR PORCHES. SEE ASTM C-1063 FOR |
| | FASTENERS, TYPE, SIZE AND SPACING. |
| | SECTION 2504.2 FBC 2001. |
| | 5-CLARIFY GARAGE DOOR DETAIL. SEE DETAIL |
| | 1/DS-1 AND DETAIL 4/S4. |
| | 6-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ROOF TILE PRODUCT APPROVAL SUBMITTED |
| | IS NOT GOOD. IT WAS DELETED FROM SBCCI |
| | 7-UPDATE ALL CONNECTORS AS REQUIRED. |
| | HUGHES OR SEMCO ARE OUT OF BUSINESS. |
| | 8-APPLY FOR SEPARATE PERMITS FOR UNITS |
| | TO HAVE SCREEN ENCLOSURES. |
| | |
| | NOTES: |
| | *DRAWINGS AND COMMENTS TO BE FILED UNDER |
| | PERMIT #02031076. |
| | *THESE COMMENTS APPLY TO PERMIT #S: |
| | 02031076, 02031077, 02031078 AND |
| | 02031080. |