| 2002-04-06 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT # 02031076 |
| | LOTS: 75-78 |
| | 8596 LINYARD CAY |
| | |
| | FL CODE= 2001 FLORIDA BUILDING CODE |
| | FR HOUS= FAIR HOUSING ACT |
| | |
| | 1)- SOILS REPORT NOT SIGNED & SEALED, |
| | 61G15-23.002 REQUIRES THE PROFESSIONAL |
| | ENGINEER SHALL SIGN HIS NAME AND AFFIX |
| | HIS SEAL TO ALL PLANS SPECIFICATIONS, |
| | REPORTS OR DOCUMENTS PREPARED OR ISSUED |
| | BY SAID REGISTRANT AND BEING FILED FOR |
| | PUBLIC RECORD. |
| | |
| | 2)- STRUCTURAL CUT SECTIONS MISSING A |
| | NEW CODE ELEMENT FL CODE 1909.3(2) |
| | CONCRETE SLABS ON GROUND CONTAINING 6X6 |
| | W1.4XW1.4 WELDED WIRE REINFORCEMENT |
| | FABRIC LOCATED IN THE MIDDLE TO THE |
| | UPPER 1/3 OF THE SLAB, SHALL BE SUPPORT- |
| | ED WITH AN APPROVED MATERIALS OR SUPPORT |
| | AT SPACINGS TO NOT EXCEED 3 FT OR IN |
| | ACCORDANCE WITH MANUFACTURES SPECIFICA- |
| | TIONS. |
| | 3)- STRUCURAL PLANS- HUGHES MANUFACTUR- |
| | ING AS WELL AS SEMCO WERE BOUGHT OUT BY |
| | USP CONNECTORS OVER A YEAR AGO. THERE |
| | IS A NEW PRODUCT REFRENCE NUMBERS AND |
| | NEW TESTING DATA. |
| | 4)- SH-1 EGRESS TYPE WINDOW NOTES: INDIC |
| | ATES A NOTE "DELTA 5" THAT ALL EXTERIOR |
| | GLAZED OPENINGS SHALL COMPLY WITH THE |
| | FBC 2001 ED CHAPTER 3? THREE IS TYPE |
| | OF OCCUPANCIES? 1005.4 EMERGENCY ESCAPE |
| | AND RESCUE OPENINGS. |
| | 5)- SHEET SH-1WINDOW SCHEDULE INDICATE |
| | A "I" 8" GLASS BLOCK TO BE A 2 HR RATING |
| | SHEET DS-1 DETAILS GLASS BLOCK IN MODEL |
| | "C". A 2 HR RATING? |
| | BUILDING PLAN REVIEW |