| 2002-04-20 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 FACBC |
| | |
| | 1) ACCORDING TO TABLE 403.1 FBC PLUMBING |
| | 1 DRINKING FOUNTAIN AND 1 SERVICE SINK |
| | SHALL BE REQUIRED. |
| | 2) SHT P-1 BUSINESS OFFICE LOUNGE, SHOW |
| | COMPLIANCE WITH SECTION 4.24 FACBC FOR |
| | SINK. |
| | 3) SHT P-1 CONDENSATE LINE TO DRYWELL |
| | SHALL HAVE A RELIEF VENT AS PIPING EXITS |
| | BLDG. SHOW DETAIL. |
| | 4) SHT P-1 GENERAL NOTES #16 CHANGE TO |
| | WATER HAMMER ARRESTORS - AIR CHAMBERS |
| | NOT APPROVED. |
| | 5) SHT P-2 ITEM #10 WATER FILTER, PLEASE |
| | SUBMIT MANUFACTURE INFORMATION. FILTER |
| | TO BE NSF APPROVED. |
| | 6) SHT P-2 ITEM #11 WATER HEATER, RELIEF |
| | VALVE DISCHARGE PIPE SHALL NOT HAVE ANY |
| | TRAPPED SECTIONS AND SHAL HAVE A VISIBLE |
| | AIR GAP OR AIR GAP FITTING LOCATED IN |
| | THE SAME ROOM AS THE WATER HEATER. FBC- |
| | PLMG SEC. 504.7 |
| | 7) SHT P-2 ITEM #12 AND ALL DENTAL EQUIP |
| | MENT SHALL HAVE BACKFLOW PROTECTION. |
| | PLEASE SUBMIT INFORMATION SHOWING HOW |
| | THIS WILL BE COMPLIED WITH. |
| | 8) SHT P-4 WATER ISOMETRIC, NOTE #9 |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | IN AN "EFFICTIVE RANGE" CLOSE TO FIXTUR- |
| | ES NOT AT TOP OF DROP AS SHOWN. PER MAN- |
| | UFACTURES INSTALLATION INSTRUCTIONS AND |
| | PDI-WH 201. |
| | 9) PLEASE SUBMIT MANUFACTURE INFORMATION |
| | ON THE DENTISTS CHAIRS TO SEE HOW WATER, |
| | WASTE, VACUUM, AND AIR ARE CONNECTED. |
| | |