2002-04-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11 FACBC
  
 1) ACCORDING TO TABLE 403.1 FBC PLUMBING
 1 DRINKING FOUNTAIN AND 1 SERVICE SINK
 SHALL BE REQUIRED.
 2) SHT P-1 BUSINESS OFFICE LOUNGE, SHOW
 COMPLIANCE WITH SECTION 4.24 FACBC FOR
 SINK.
 3) SHT P-1 CONDENSATE LINE TO DRYWELL
 SHALL HAVE A RELIEF VENT AS PIPING EXITS
 BLDG. SHOW DETAIL.
 4) SHT P-1 GENERAL NOTES #16 CHANGE TO
 WATER HAMMER ARRESTORS - AIR CHAMBERS
 NOT APPROVED.
 5) SHT P-2 ITEM #10 WATER FILTER, PLEASE
 SUBMIT MANUFACTURE INFORMATION. FILTER
 TO BE NSF APPROVED.
 6) SHT P-2 ITEM #11 WATER HEATER, RELIEF
 VALVE DISCHARGE PIPE SHALL NOT HAVE ANY
 TRAPPED SECTIONS AND SHAL HAVE A VISIBLE
 AIR GAP OR AIR GAP FITTING LOCATED IN
 THE SAME ROOM AS THE WATER HEATER. FBC-
 PLMG SEC. 504.7
 7) SHT P-2 ITEM #12 AND ALL DENTAL EQUIP
 MENT SHALL HAVE BACKFLOW PROTECTION.
 PLEASE SUBMIT INFORMATION SHOWING HOW
 THIS WILL BE COMPLIED WITH.
 8) SHT P-4 WATER ISOMETRIC, NOTE #9
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 IN AN "EFFICTIVE RANGE" CLOSE TO FIXTUR-
 ES NOT AT TOP OF DROP AS SHOWN. PER MAN-
 UFACTURES INSTALLATION INSTRUCTIONS AND
 PDI-WH 201.
 9) PLEASE SUBMIT MANUFACTURE INFORMATION
 ON THE DENTISTS CHAIRS TO SEE HOW WATER,
 WASTE, VACUUM, AND AIR ARE CONNECTED.
  