Plan Review Notes
Plan Review Notes For Permit 02031030
Permit Number 02031030
Review Stop M
Sequence Number 1
Notes
Date Text
2002-04-11 00:00:00 
  
 1.2001 FBC, MECHANICAL 401.5, OUTSIDE
 AIR EXHAUST & INTAKE OPENINGS SHALL
 BE A MINIMUM OF 10 FT FROM LOT LINES
 OR BUILDINGS ON THE SAME LOT.
  
 2.AS PER 2001 FBC, MECHANICAL 401.5.2,
 EXHAUST AIR SHALL NOT BE DIRECTED ON
 TO WALKWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.