| Plan Review Notes For Permit 02031030 |
| Permit Number |
02031030 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-04 00:00:00 | A) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWINGS. BUILDING ADDRESS | | | REQUIRED. | | | B) ALL STORAGE AND MECHANICAL ROOMS | | | ARE TO BE FIRE RATED AND BE EQUIPPED | | | WITH AT C LABELED FIRE DOORS SINCE | | | NO FIRE SPRINKLERS ARE PRESENT. | | | C) EXITING NOTED THRU PRIVATE OFFICE. | | | THE DOOR LEADING INTO THE PRIVATE | | | OFFICE CANNOT BE SUBJECT TO LOCKING | | | AND ALSO NO FURNITURE IS TO BE PLACED | | | IN FRONT OF THE EXIT DOORS. | | | D) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFOMATION FOR WALLS | | | AND CEILINGS. | | | E) PLEASE INDICATE OCCUPANT LOAD FOR | | | BUILDING, SINCE SOME CORRIDORS ARE LESS | | | THAN 44" WIDE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|