Review Stop FIRE
Sequence Number 1
Notes
Date Text
2002-04-04 00:00:00A) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS
 REQUIRED.
 B) ALL STORAGE AND MECHANICAL ROOMS
 ARE TO BE FIRE RATED AND BE EQUIPPED
 WITH AT C LABELED FIRE DOORS SINCE
 NO FIRE SPRINKLERS ARE PRESENT.
 C) EXITING NOTED THRU PRIVATE OFFICE.
 THE DOOR LEADING INTO THE PRIVATE
 OFFICE CANNOT BE SUBJECT TO LOCKING
 AND ALSO NO FURNITURE IS TO BE PLACED
 IN FRONT OF THE EXIT DOORS.
 D) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION INFOMATION FOR WALLS
 AND CEILINGS.
 E) PLEASE INDICATE OCCUPANT LOAD FOR
 BUILDING, SINCE SOME CORRIDORS ARE LESS
 THAN 44" WIDE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910