| 2002-04-17 00:00:00 | THIS BUILDING IS LOCATED IN AN A5 FLOOD |
| | ZONE WITH A BFE OF 7.0' NGVD.THE |
| | LOWEST OCCUPIABLE FLOOR MUST BE AT OR |
| | ABOVE 7.5'NGVD. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY FOR THE CITY, THE |
| | PERMIT PLANSSTAMPED BY THAT OFFICE AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO |
| | THE PERMIT APPLICATION.CALL |
| | 561-233-5025 FOR MORE INFORMATION. |
| | |
| | AT TIME OF PERMIT APPLICATION PROVIDE A |
| | RECENT, SIGNED, SEALED AND DATED |
| | PROPERTY SURVEY INCLUDING ELEVATIONS. |
| | |
| | THE HC RAMP AS SHOWN DOES NOT COMPLY |
| | WITH FBC 11-4.8. |
| | |
| | ALL OF THE REMODELED PORTIONS OF THE |
| | BUILDING MUST COMPLY WITH 11-4.1 |
| | THROUGH 11-4.35.THE PLANS AS SHOWN DO |
| | NOT COMPLY. |
| | |
| | THE EXTERIOR DOORS AT THE PRIVATE |
| | OFFICEAND LOBBY MUST COMPLY WITH FBC |
| | 1012.1.3 FOR LANDINGS. |
| | |
| | THE PERMIT PLANS SHOULD INDICATE THE |
| | OVERFLOW SCUPPERS IN THE PARAPET WALLS |
| | AS PROVIDED FOR IN FBC 1511.6.4.3. |
| | |
| | PROVIDE A STRUCTURAL ANALYSIS OF THE |
| | EXISTING ROOF TRUSSES DEMONSTRATING |
| | THEIR SUITABILILTY TO ASSUME THE NEW |
| | LOADS THAT WILL BE IMPOSED. |
| | |
| | ADDITIONAL CONSTRUCTION DETAILS FOR THE |
| | DECORATIVE CAST COLUMNS AND GABLE END |
| | TRUSSES WILL BE NECESSARY. |