2002-04-17 00:00:00THIS BUILDING IS LOCATED IN AN A5 FLOOD
 ZONE WITH A BFE OF 7.0' NGVD.THE
 LOWEST OCCUPIABLE FLOOR MUST BE AT OR
 ABOVE 7.5'NGVD.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY FOR THE CITY, THE
 PERMIT PLANSSTAMPED BY THAT OFFICE AND
 A COPY OF THE PAID RECEIPT ATTACHED TO
 THE PERMIT APPLICATION.CALL
 561-233-5025 FOR MORE INFORMATION.
  
 AT TIME OF PERMIT APPLICATION PROVIDE A
 RECENT, SIGNED, SEALED AND DATED
 PROPERTY SURVEY INCLUDING ELEVATIONS.
  
 THE HC RAMP AS SHOWN DOES NOT COMPLY
 WITH FBC 11-4.8.
  
 ALL OF THE REMODELED PORTIONS OF THE
 BUILDING MUST COMPLY WITH 11-4.1
 THROUGH 11-4.35.THE PLANS AS SHOWN DO
 NOT COMPLY.
  
 THE EXTERIOR DOORS AT THE PRIVATE
 OFFICEAND LOBBY MUST COMPLY WITH FBC
 1012.1.3 FOR LANDINGS.
  
 THE PERMIT PLANS SHOULD INDICATE THE
 OVERFLOW SCUPPERS IN THE PARAPET WALLS
 AS PROVIDED FOR IN FBC 1511.6.4.3.
  
 PROVIDE A STRUCTURAL ANALYSIS OF THE
 EXISTING ROOF TRUSSES DEMONSTRATING
 THEIR SUITABILILTY TO ASSUME THE NEW
 LOADS THAT WILL BE IMPOSED.
  
 ADDITIONAL CONSTRUCTION DETAILS FOR THE
 DECORATIVE CAST COLUMNS AND GABLE END
 TRUSSES WILL BE NECESSARY.