Plan Review Notes
Plan Review Notes For Permit 02030952
Permit Number 02030952
Review Stop E
Sequence Number 1
Notes
Date Text
2002-04-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE THE CODES REFERENCE-
 D IN NOTES, AREALL FROM THE "96" NEC
 PLEASE NOTE , 110-16, 250-95 AND 250-60
 ARE NOW 110-26,250-122,250-140.
 PLEASE NOTE THAT WE HAVE BEEN UNDER THE
 "99" NEC SINCE MARCH 2000.
  
 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12. AS OF JAN 1ST,
 2002.
  
 3)NOTE: PLEASE NOTE THAT A SD NEEDS TO
 BE ADDED BETWEEN BEDROOM #2 AND MASTER
 BEDROOM.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372