| Plan Review Notes For Permit 02030952 |
| Permit Number |
02030952 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-03 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE NOTE THE CODES REFERENCE- | | | D IN NOTES, AREALL FROM THE "96" NEC | | | PLEASE NOTE , 110-16, 250-95 AND 250-60 | | | ARE NOW 110-26,250-122,250-140. | | | PLEASE NOTE THAT WE HAVE BEEN UNDER THE | | | "99" NEC SINCE MARCH 2000. | | | | | | 2)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTION PER 210-12. AS OF JAN 1ST, | | | 2002. | | | | | | 3)NOTE: PLEASE NOTE THAT A SD NEEDS TO | | | BE ADDED BETWEEN BEDROOM #2 AND MASTER | | | BEDROOM. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|