| Plan Review Notes For Permit 02030862 |
| Permit Number |
02030862 |
|
| Review Stop |
FS |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-19 00:00:00 | A) THE SITE PLAN INDICATES A FIRE HYD. | | | LOCATED TO THE REAR OF BUILDING ONE. | | | IT IS NOT CLEAR IF THE FIRE LINE THAT | | | THE HYDRANT IS CONNECTED TO IS LOOPED | | | OR DEAD-ENDS. THE BROKEN LINE JUST | | | STOPS, PLEASE CLARIFY. | | | B) THE PLAN SEEMS TO INDICATE STORAGE | | | HEIGHTS OF AT LEAST TWENTY FIVE FEET. | | | PLEASE INDICATE STORAGE ARRANGEMENTS | | | AND AISLE WIDTHS. | | | C) PLEASE INDICATE ON THE PLANS THAT | | | THE 1999 EDITION OF NFPA 13 IS THE | | | REFERENCE DOCUMENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|