| 2002-04-18 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 104.2.1THE TITLE BLOCKS ON THE |
| | PLANS SHOW AN INCORRECT ADDRESS.AMEND |
| | TO READ '245 WALTON BLVD' FOR PUBLIC |
| | RECORD. |
| | |
| | 4) FBC 13-103.0ENERGY CODE COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE CODE COMPLIANCE FORMS. |
| | |
| | 5) FBC 1606.1.4SUBMIT A PRODUCT |
| | APPROVAL FOR THE NEW WINDOWS.IF THE |
| | PROPOSED WINDOWS REQUIRE HURRICANE |
| | MISSILE IMPACT PROTECTION, THEN A |
| | SHUTTER PRODUCT APPROVAL WILL ALSO BE |
| | REQUIRED. |
| | |
| | 6) FBC 1804.6.3.1CRAWL SPACE |
| | VENTILATION.A MINIMUM OF 2 SQFT OF |
| | CROSS VENTILATION SHALL BE PROVIDED. |
| | THE VENTILATION OPENINGS SHALL BE |
| | PROTECTED WITH CORROSION RESISTANT WIRE |
| | MESH WITH APERTURES OF NOT LESS THAN |
| | 1/4" NOR MORE THAN 1/2" IN ANY DIMENSION |
| | |
| | 7) FBC* 104.2.1ANNOTATE THE PLANS TO |
| | DESCRIBE HOW THE CONCRETE MASONRY UNIT |
| | BLOCKING AROUND THE NEW WINDOW WILL BE |
| | TIED TO THE EXISTING MASONRY AS A SECURE |
| | SUBSTRATE FOR THE NEW WINDOW/SHUTTERS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |