Plan Review Notes
Plan Review Notes For Permit 02030851
Permit Number 02030851
Review Stop E
Sequence Number 1
Notes
Date Text
2002-03-20 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY,E-1 MENTIONS
 ELECTRICAL SITE PLAN? PLEASE NOTE THAT
 NO "ELECTRICAL SITE" WORK IS SHOWN?
 LANDSCAPE LIGHTING/LIGHTING FOR PARKING
 LOT(S) ETC. PLEASE CLARIFY.
  
 2)NOTE: PLEASE CLARIFY LOCATION OF TWO
 A/C COND UNITS SHOWN ON MDP?CU-1/CU-2
 PLEASE NOTE THAT THESE NEED TO BE SHOWN
 ON POWER PLAN AND NEED TO HAVE DISC`S
 PER 440-11.
  
 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS
 PER 220-3,220-11. PLEASE NOTE WATTS/PER
 SQ FT. ETC. PLEASE NOTE THAT ALL
 CONTINUOUS LOADS AT 125% PER 215-2,3/
 230-42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REIVEW
 561-659-8096 EXT 8372
  
  
 PLEASE NOTE THAT NOTES FROM FIRST REVIEW
 ASKED FOR LOAD CALCULATIONS TO BE SHOWN.