| Plan Review Notes For Permit 02030851 |
| Permit Number |
02030851 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-20 00:00:00 | **************** UNSAT *************** | | | | | | 1)NOTE: PLEASE CLARIFY,E-1 MENTIONS | | | ELECTRICAL SITE PLAN? PLEASE NOTE THAT | | | NO "ELECTRICAL SITE" WORK IS SHOWN? | | | LANDSCAPE LIGHTING/LIGHTING FOR PARKING | | | LOT(S) ETC. PLEASE CLARIFY. | | | | | | 2)NOTE: PLEASE CLARIFY LOCATION OF TWO | | | A/C COND UNITS SHOWN ON MDP?CU-1/CU-2 | | | PLEASE NOTE THAT THESE NEED TO BE SHOWN | | | ON POWER PLAN AND NEED TO HAVE DISC`S | | | PER 440-11. | | | | | | 3)NOTE: PLEASE SHOW LOAD CALCUALTIONS | | | PER 220-3,220-11. PLEASE NOTE WATTS/PER | | | SQ FT. ETC. PLEASE NOTE THAT ALL | | | CONTINUOUS LOADS AT 125% PER 215-2,3/ | | | 230-42 ETC. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REIVEW | | | 561-659-8096 EXT 8372 | | | | | | | | | PLEASE NOTE THAT NOTES FROM FIRST REVIEW | | | ASKED FOR LOAD CALCULATIONS TO BE SHOWN. |
|