| Plan Review Notes For Permit 02030850 |
| Permit Number |
02030850 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-03-20 00:00:00 | ****************** UNSAT *************** | | | | | | PLEASE NOTE THAT NOW COMPLETE PLANS ARE | | | BEING SUBMITTED FOR REVIEW FROM 10/30/01 | | | | | | PLEASE NOTE THAT PLANS STILL HAVE NOTES | | | FROM FIRST REVIEW TO BE ADDRESSED. | | | | | | 1)NOTE: PLEASE NOTE THAT PLANS MUST BE | | | SIGNED DATED AND SEALED BY THE ARCH`S/ | | | ENGINEER OF RECORD. PER FAC/FS 471.025 | | | 481.221. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS | | | PER 220-11/220-10 PLEASE SHOW AS PER | | | W=SQ FT ETC.PLEASE NOTE ALL CONTINUOUS | | | LOADS AT 125%. 215-2,3/230-42,,,,,, | | | | | | 3)NOTE: PLEASE NOTE THAT DSB-7 AND DSB-8 | | | ARE MISSING FROM DISC SW SCHEDULE. | | | | | | 4)NOTE: PLEASE NOTE THAT COND UNITS 1&2 | | | LOCATIONS ARE NOT SHOWN ON E-3. | | | PLEASE SHOW, SHOW DISC`S PER 440-11 | | | | | | 5)NOTE: PLEASE NOTE THAT SHEET E-1 SAYS | | | "ELECTRICAL SITE PLAN" PLEASE CALRIFY | | | THERE IS NO ELECTRICAL SITE ELECTRICAL | | | SHOWN? LIGHTING/LANDSCAPE LTS ETC?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|