2002-03-20 00:00:00****************** UNSAT ***************
  
 PLEASE NOTE THAT NOW COMPLETE PLANS ARE
 BEING SUBMITTED FOR REVIEW FROM 10/30/01
  
 PLEASE NOTE THAT PLANS STILL HAVE NOTES
 FROM FIRST REVIEW TO BE ADDRESSED.
  
 1)NOTE: PLEASE NOTE THAT PLANS MUST BE
 SIGNED DATED AND SEALED BY THE ARCH`S/
 ENGINEER OF RECORD. PER FAC/FS 471.025
 481.221.
  
 2)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER 220-11/220-10 PLEASE SHOW AS PER
 W=SQ FT ETC.PLEASE NOTE ALL CONTINUOUS
 LOADS AT 125%. 215-2,3/230-42,,,,,,
  
 3)NOTE: PLEASE NOTE THAT DSB-7 AND DSB-8
 ARE MISSING FROM DISC SW SCHEDULE.
  
 4)NOTE: PLEASE NOTE THAT COND UNITS 1&2
 LOCATIONS ARE NOT SHOWN ON E-3.
 PLEASE SHOW, SHOW DISC`S PER 440-11
  
 5)NOTE: PLEASE NOTE THAT SHEET E-1 SAYS
 "ELECTRICAL SITE PLAN" PLEASE CALRIFY
 THERE IS NO ELECTRICAL SITE ELECTRICAL
 SHOWN? LIGHTING/LANDSCAPE LTS ETC??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372