2002-03-13 00:00:00****************UNSAT!!*****************
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW:
  
 1}PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} NUMBER AND SIZE OF CONDUCTORS IN:
 A)1-1/4"PVC
 B)3" PVC.
  
 3} OVERCURRENT PROTECTION OF THESE
 CONDUCTORS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392