2002-04-24 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW
 A) FBC-2001 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 B)
 FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 C)
 FBC-2001 SEC 424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MI8NIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 D)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 E)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 2) THIS INFORMATION WAS REQUESTED ON
 PREVIOUS REVIEW. SOME INFORMATION WAS
 SUPPLIED, SOME PARTIALLY SUPPLIED. IF
 FAX NOT RECIEVED I DID NOT KNOW. SEE
 ATTACHED SHEET.
 3) PLEASE PUT ALL PAGES TOGETHER TO FORM
 TWO COMPLETE SETS OF PLANS. LOOSE SHEETS
 CAN GET LOST.
  
 REVIEW BY KEN STEVENS