| Plan Review Notes For Permit 02030788 |
| Permit Number |
02030788 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-04-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 424.2 SWIMMING POOLS | | | | | | 1) PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING IN- | | | FORMATION REQUIRED FOR PLAN REVIEW | | | A) FBC-2001 SEC 424.2.6.6 ENTRAPMENT | | | PROTECTION FOR SUCTION INLETS. (DETAIL) | | | B) | | | FBC-2001 SEC 424.2.6.6.3 (1,2,3) ENTRAP- | | | MENT AVOIDANCE. (DETAIL) | | | C) | | | FBC-2001 SEC 424.2.6.6.4 MINIMUM OF TWO | | | SUCTION INLETS SHALL BE PROVIDED FOR EA | | | PUMP. SEPARATED BY A MI8NIMUM OF 3 FEET | | | OR LOCATED ON TWO DIFFERENT PLANES. | | | (DETAIL) | | | D) | | | FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL | | | ORD. #2853-95, BACKFLOW REQUIRED ON | | | WATER SERVICE. (ADD TO NOTES) | | | E) | | | FBC-2001 SEC 424.2.12.1 PRESSURE TESTS. | | | PER MANUFACTURE RECOMMENDATIONS, NO AIR | | | TEST SHALL BE APPROVED FOR PVC PIPE AND | | | FITTINGS. (ADD TO NOTES) | | | 2) THIS INFORMATION WAS REQUESTED ON | | | PREVIOUS REVIEW. SOME INFORMATION WAS | | | SUPPLIED, SOME PARTIALLY SUPPLIED. IF | | | FAX NOT RECIEVED I DID NOT KNOW. SEE | | | ATTACHED SHEET. | | | 3) PLEASE PUT ALL PAGES TOGETHER TO FORM | | | TWO COMPLETE SETS OF PLANS. LOOSE SHEETS | | | CAN GET LOST. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|