| Plan Review Notes For Permit 02030743 |
| Permit Number |
02030743 |
|
| Review Stop |
FIRE |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2002-08-21 00:00:00 | 1) ALL UNDERGROUND FIRE LINES ARE TO | | | BE INSTALLED IN ACCORDANCE WITH | | | NFPA 24. | | | | | | 2) NO CONTROL VALVES ARE ALLOWED TO BE | | | INSTALLED IN THE FIRE DEPARTMENT | | | CONNECTION. | | | | | | 3) A CHECK VALVE IS REQUIRED IN THE | | | FIRE DEPARTMENT CONNECTION. | | | | | | 4) UNDERGROUND FIRE LINES ARE TO BE | | | PROPERLY RESTRAINED IN ACCORDANCE WITH | | | NFPA 24. | | | | | | 5) ALL LINES ARE TO BE PRESSURE TESTED | | | IN ACCORDANCE WITH NFPA 24. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|