| Plan Review Notes For Permit 02030743 |
| Permit Number |
02030743 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-06-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 11 | | | FBC-2001 PLUMBING | | | FBC-2001 FUEL GAS | | | | | | 1) PLANS TO BE ROUTED TO DBPR HOTEL AND | | | RESTURANT DIVISION FOR PLAN REVIEW BE- | | | FORE PLUMBING PLAN REVIEW. (RESPONSE NO- | | | TED) | | | 2) SANITARY PIPE SIZE NOT CORRECT. ONLY | | | 180 FU FOR 4" PIPE @ 1/8" PER FOOT FALL. | | | PLEASE ADJUST PIPE SIZE.(TALKED TO ENG.) | | | 3) SHT P-401 SANT RISER DIAGRAM FLOOR | | | DRAIN AT WATER TO REFLECT FLOOR PLAN & | | | SHOW AS FLOOR SINK. (DISCUSSED WITH ENG) | | | 4) SHT P-402 WATER RISER DIAGRAM, ALL | | | WATER HAMMER ARRESTORS NOT LOCATED NEAR | | | FIXTURES. PLEASE CHANGE (DISCUSSED WITH | | | ENG.) | | | 5) GAS REVIEW NOT DONE - ENGINEER SAYS | | | INFORMATION SHALL BE SUBMITTED WITH GAS | | | PERMIT APPLICATION. | | | 6) CONDENSATE SHALL BE PIPED SEPARATE | | | FROM BLDG. SHT P-201 COLS. B/11 EXCEPT- | | | ION. (DISCUSSED WITH ENG.) | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|