| Date |
Text |
| 2002-05-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) SHT P-101 ICE MACHINE DETAIL - FILTER |
| | SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN |
| | FORMATION. |
| | 2) SHT P-101 SUBMERSIBLE SUMP PUMP, MAN- |
| | UFACTURE INFO SHOWING LISTING REQD. |
| | 3) SHTS P-202, 203, ALL |
| | CONDENSATE SHALL BE PIPED SEPARATELY TO |
| | THE OUTSIDE OF BLDG AND TIED INTO STORM |
| | OR DRYWELL. SEE COLS. 14-A/B, 11-B/C |
| | SHT P-202. SEE RM #G-05 SHT P-203. |
| | 4) SHT P-201, ELEVATOR #1 DRAINS TO RAIN |
| | WATER CATCH BASIN AND HAS NO BACKWATER |
| | VALVE. ELEVATOR #3 HAS AN AREA DRAIN |
| | WITH A BACKWATER VALVE IN LINE AND DIS- |
| | CHARGES TO AN OIL AND SAND INTERCEPTOR. |
| | PLEASE CHECK WITH ELEVATOR COMPANY TO |
| | SEE IF THIS IS ACCEPTABLE TO HOOK UP |
| | DIRECTLY IN ELEVATOR PIT. |
| | 5) PLEASE ROUTE PLANS THROUGH DEPT OF |
| | BUSINESS HOTEL AND RESTURANT DIVISION |
| | FOR PLAN REVIEW BEFORE RESUBMITTING FOR |
| | PLAN REVIEW. |
| | 6) SHT P-302 ITEMS #82/115 FILTERS, NSF |
| | APPROVAL REQUIRED. SUBMIT MANUF. INFO |
| | 7) PLEASE SHOW FIXTURE UNITS AS THEY |
| | ACCUMULATE ON THE SANITARY RISER DIAGRAM |
| | 8) SHT P-401 MECH ROOM M-13 FLOOR DRAIN |
| | NOT SHOWN ON SANT RISER DIAGRAM. |
| | 9) SHT P-401 SANT RISER FOR MECH ROOMS |
| | M-13, 2-28, 3-016 NOT SHOWN ON SANT RIS- |
| | ER DIAGRAM. PLEASE SHOW RISER AS SHOWN |
| | ON FLAT DRAWING IN WOMENS ROOM G-39 & |
| | MENS ROOM G-40, PICKING UP ALL MECH RMS |
| | AND VENT THROUGH ROOF. |
| | 10) SHT P-401 FLOOR DRAIN ON SANT RISER |
| | DIAGRAM SHOULD BE CHANGED TO FLOOR SINK |
| | AT WATER HEATER. (CHANGED ON FLOOR PLAN) |
| | 11) SHT P-402 KITCHEN EQUIP PLMG SCHED., |
| | SHOWS 1 FRYER, GAS RISER SHOWS 2. PLEASE |
| | CLAIRFY. |
| | 12) SHT P-402 WATER RISER DIAGRAM, ALL |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR FIXTURES IN AN "EFFECTIVE RANGE" |
| | NOT AT TOP OF DROP. LOCATE PER MANUFACT- |
| | URE INSTALLATION INSTRUCTIONS AND PDI- |
| | WH 201. (SOME CHANGED NOT ALL) |
| | 13) ALL GAS PERMIT APPLICATION REQUIRE- |
| | MENTS FROM PREVIOUS REVIEW HAVE NOT BEEN |
| | ADDRESSED. PLEASE SUBMIT INFORMATION. |
| | 14) SHT A-106 & A-210 CEO TOILET ROOM |
| | CAN NOT CHANGE FLOOR PLANS TO COMPLY |
| | WITH ADAPTABILITY. STRUCTURAL CHANGES |
| | FOR ADAPTABILITY IS NOT APPROVED. |
| | PLEASE SHOW DETAILS FOR ADAPTABILITY. |
| | SHOWER CURB TO BE NO MORE THAN 1/2", |
| | BACKING FOR ALL GRAB BARS, SPACING FOR |
| | W/C ECT. |
| | 15) TO WHERE DOES THE RAIN WATER FROM |
| | THE CANOPY DRAIN? |
| | |