| 2002-05-29 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS |
| | ARE NUMBERED AS PER THE BUILDING PLAN |
| | REVIEW OF 4/12/02: |
| | |
| | 1) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| | A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| | IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY, THE PLANS STAMPED BY THEM AND A |
| | COPY OF THE RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 104.2.4CONTRARY TO THE LETTER |
| | OF RESPONSE, DATED 4/22/02, NO SIGNED |
| | AND SEALED SITE SURVEY DRAWING WAS |
| | SUBMITTED. |
| | |
| | 4) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| | FBC* 104.2.1.1 ROOF COVERING PRODUCT |
| | APPROVAL SHALL BE SUBMITTED FOR THE ROOF |
| | COVERING SYSTEM TO BE USED (FBC 1504.3) |
| | |
| | 7) RESPONSE LETTER OF 4/22/02 IS NOTED. |
| | FBC 1606.1.4 WINDOW AND DOOR PRODUCT |
| | APPROVALS.SUBMIT PRODUCT APPROVALS FOR |
| | THE EXTERIOR DOOR AND WINDOW SYSTEMS TO |
| | BE USED. |
| | |
| | 9) FBC 13-103THREE COPIES OF THE HVAC |
| | LOAD ANALYSIS WERE RECEIVED BUT ENERGY |
| | CODE COMPLIANCE FORMS SHALL BE SUBMITTED |
| | TO DEMONSTRATE COMPLIANCE WITH THE CODE. |
| | |
| | 11) FBC 1019.1.1EXIT FROM ASSEMBLY RMS |
| | SHEET LS-105, SECOND FLOOR.ADD PAINTED |
| | STRIPES AND WARNING: FIRE EGRESS, KEEP |
| | CLEAR, ON SHEETS LS-103 AND A-103, |
| | BETWEEN DOOR G22 AND THE EXTERNAL RAMP |
| | AND STEPS. |
| | |
| | 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED' |
| | ROOM, SHEET LS-106.IF, AS STATED IN |
| | THE LETTER OF RESPONSE, THE EGRESS |
| | CAPACITY HAS BEEN ASSESSED BASED ON |
| | OFFICE USE, CHANGE THE ROOM DESIGNATION |
| | FROM 'UNASSIGNED' TO 'OFFICE' ON |
| | SHEETS LS-106 AND A-106. |
| | |
| | 17) IT IS NOTED FROM THE LETTER OF |
| | RESPONSE, DATED 4/22/02, THAT STAIR #3 |
| | IS NOT INTENDED FOR USE AS AN EXIT. |
| | THEREFOR THE COMMON PATH OF TRAVEL |
| | (FBC 202 AND FBC 1020.6) FROM COMMUNITY |
| | CONFERENCE ROOM 3-003 AND RECEPTION |
| | 3-002 MAY EXCEED 100 FT.SHOW THE |
| | PROPOSED FURNITURE LAYOUT FOR THESE |
| | ROOMS ON THE LIFE SAFETY PLAN AND SHOW |
| | THAT THE COMMON PATH OF TRAVEL TO THE |
| | NORTH SECTION OF CORRIDOR 3-010 DOES NOT |
| | EXCEED 100 FT.ALTERNATIVELY, AMEND THE |
| | EGRESS SIGNS AND DOOR LOCKS TO PROVIDE A |
| | SEPARATE ROUTE VIA CORRIDOR 3-024. |
| | |
| | 21) FBC 104.2.1 EXTERIOR ALUMINUM |
| | CLADDING PANELS.THE REVISED DETAIL |
| | 8/A-705 STILL DOES NOT SHOW THE MEANS OF |
| | ATTACHING THE ALUMINUM FACED PLYWOOD |
| | PANELS TO THE BUILDING FACADE. |
| | |
| | 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING. |
| | ADD A NOTE, TO THE PARKING LEVEL PLANS, |
| | STATING THAT THE VALET PARKING SERVICE |
| | WILL BE THE MEANS OF SATISFYING THE |
| | REQUIREMENT FOR ACCESSIBLE PARKING. |
| | |
| | 24) FBC 11-4.8LEVEL 1 PARKING, SHEET |
| | LS-101.CONTRARY TO THE LETTER OF |
| | RESPONSE, THE ELEVATOR LOBBY IS SHOWN AS |
| | EL 80'-6", NOT EL 80'-0", SO THERE IS AN |
| | ELEVATION CHANGE.SHOW/ANNOTATE THE |
| | RAMP FROM THE PARKING LEVEL UP TO THE |
| | ELEVATOR LOBBY LEVEL FOR ACCESSIBILITY. |
| | |
| | 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS. |
| | SHEET A-810, DETAIL 6 RAIL AT WALL. |
| | WITH REFERENCE TO THE LETTER OF RESPONSE |
| | DATED 4/22/02, THE QUOTATION FROM THE |
| | CODE IS INCOMPLETE.THE PARAGRAPH GOES |
| | ON TO REQUIRE THAT THE HANDRAIL CONTINUE |
| | TO SLOPE BEYOND THE BOTTOM RISER FOR A |
| | DISTANCE EQUAL TO THE WIDTH OF ONE TREAD |
| | AND THEN EXTEND HORIZONTALLY FOR 12" |
| | (FIG. 19C).ON SHEET A810, NEITHER THE |
| | SLOPED OR HORIZONTAL EXTENSIONS ARE |
| | DIMENSIONED INDIVIDUALLY TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 29) FBC 11-4.31PUBLIC TELEPHONES.THE |
| | RESPONSE RELATING TO 'FOOTPRINT'IS NOTED |
| | BUT COMPLIANCE SHALL BE DEMONSTRATED BY |
| | ADDING DIMENSIONS TO THE PLANS, |
| | INCLUDING SHEET A103 (AT G-03 AND G-09) |
| | AND SHEET A105 (AT 2-03, TEL. ALCOVE). |
| | THE PLANS SHALL ALSO BE AMENDED TO SHOW |
| | THE INSTALLATION HEIGHT AND FACILITIES |
| | PROVISION GIVEN IN FBC 11-4.1.3(17). |
| | |
| | 30) FBC 11-4.15DRINKING FOUNTAINS. THE |
| | RESPONSE RELATING TO 'FOOTPRINT'IS NOTED |
| | BUT THE PLANS SHALL BE AMENDED TO |
| | DEMONSTRATE COMPLIANCE WITH THE SPOUT |
| | HEIGHT AND VERTICAL CLEARANCE |
| | REQUIREMENTS (FIG. 27A) |
| | |
| | 31) FBC 11-4.19LAVATORIES.AMEND THE |
| | PLANS TO SHOW THE LAVATORY LEGROOM |
| | CLEARANCES AND A MAXIMUM HEIGHT OF 40" |
| | TO THE BASE OF THE MIRROR (FIG. 31) |
| | |
| | 32) FBC 11-4.16WATER CLOSET.THE |
| | REVISIONS TO SHEETS A-208, A-209 AND |
| | A-210 ARE NOTED, BUT NORTH AND WEST |
| | ELEVATIONS, 3/A-208, STILL SHOW TOILET |
| | SEATS AT 20" ABOVE FLOOR.AMEND TO 18". |
| | |
| | 34) FBC 11-4.35 DRESSING ROOMS, SHEET |
| | A-209.THE AMENDMENTS MADE ARE NOTED, |
| | BUT THE PLANS SHALL BE AMENDED TO |
| | DEMONSTRATE COMPLIANCE WITH 11-4.35.5 |
| | WHICH REQUIRES THE PROVISION OF A |
| | COMPLIANT FULL LENGTH MIRROR. |
| | |
| | 35) FBC 403.1.4.1BARS TO COMPLY WITH |
| | FBC 11-4.5.2.THE PROPOSAL TO PROVIDE |
| | BAR SERVICE AT ACCESSIBLE SEATING |
| | ADJACENT EACH BAR IS NOTED.ADD A NOTE |
| | TO THE PLANS, AT EACH BAR LOCATION, TO |
| | DEMONSTRATE THE PROVISION OF ACCESSIBLE |
| | SEATING AND ASSOCIATED BAR SERVICE. |
| | |
| | NOTE: COMMENTS 2, 3, 5, 6, 7, 14 AND 17 |
| | FROM THE FIRE DEPARTMENT PLAN REVIEW #2, |
| | DATED 5/21/02, SHALL ALSO BE ADDRESSED. |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |