| 2002-04-09 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | |
| | 1) SHT P-101 ICE MACHINE DETAIL-ALL IN- |
| | DIRECT WASTE SHALL DRAIN TO FLOOR SINK, |
| | NOT FLOOR DRAIN AS SHOWN |
| | 2) SHT P-101 ICE MACHINE DETAIL - FILTER |
| | SHALL BE NSF COMPLIANT. SUBMIT MANUF. IN |
| | FORMATION. |
| | 3) SHT P-101 SUBMERSIBLE SUMP PUMB - |
| | MANUFACTURE INFORMATION WITH LISTING REQ |
| | 4) SHT P-101 PLMG FIXTURE SCHED AND SPEC |
| | FUNNEL FLOOR DRAIN NOT APPROVED. DELETE |
| | 5) SHT P-201 SEPARATE PERMIT REQUIRED |
| | FOR OIL AND SAND INTERCEPTOR - TO BE |
| | SIZED BY RODNEY COMPO ENVIRONMENTAL |
| | COMPLIANCE (561) 837-4074. |
| | 6) SHT P-201 SEPARATE PERMIT REQUIRED |
| | FOR GREASE TRAP - TO BE SIZED BY RODNEY |
| | COMPO, ENVIRONMENTAL COMPLIANCE (561) |
| | 837-4074 WASTE ORD. #2938-96 |
| | 7) SHTS P-201, 202, 203, 204, & 205 - |
| | ALL CONDENSATE FROM A/C SHALL BE PIPED |
| | SEPARATE TO OUTSIDE OF BLDG AND BE TIED |
| | INTO SANITARY OR DRYWELL WITH A RELIEF |
| | VENT INSTALLED AS PIPE EXITS BLDG. (SEE |
| | COL'S 14-B/C, 14-A/B, 11-B/C - P-202 COL |
| | 2-B/C, 11-B FUNNEL DRAIN NOT APPROVED, |
| | P-203 COL 11-B CONDENSATE TO JANITOR |
| | ROVED, 2-A CONDENSATE TO HUB DRAIN NOT |
| | APPROVED, RM# G-05 COND TO SANT NOT APP- |
| | ROVED - P-204 COL 1/2 - B/C COND. TO |
| | SANT NOT APPROVED, COL 2-D CONDENSATE |
| | FROM WALK IN COOLER SHALL DRAIN TO FLOOR |
| | SINK, FUNNEL FLOOR DRAIN NOT APPROVED, |
| | COL 12-C, SHT P-205 COL 1/2 - B/C, SHT |
| | P-206 IN MECH ROOM, SHT P-207 ELEV ROOM) |
| | 8) SHT P-201, ELEVATOR #1 DRAINS TO RAIN |
| | WATER CATCH BASIN AND HAS NO BACKWATER |
| | VALVE. ELEVATOR #3 HAS AN AREA DRAIN |
| | WITH A BACKWATER VALVE IN LINE AND DIS- |
| | CHARGES TO AN OIL AND SAND INTERCEPTOR. |
| | PLEASE CHECK WITH ELEVATOR COMPANY IF |
| | THIS WILL BE EXCEPTABLE TO HOOK THESE |
| | UP DIRECTLY TO ELEVATOR PIT. |
| | 9) SHT P-204 WATER HEATER DETAIL, P/T |
| | RELIEF DISCHARGE SHALL NOT DRAIN TO |
| | FLOOR DRAIN. FLOOR SINK REQUIRED FOR ALL |
| | INDIRECT WASTE. FBC 2001 SEC 802.3 |
| | 10) SHT P-204 WATER HEATER DETAIL, SHUT |
| | OFF VALVE REQUIRED ON EACH SIDE OF CIRC. |
| | PUMP. |
| | 11) SHT P-206 SAFE WASTE DETAIL, NOT |
| | APPROVED - DELETE |
| | 12) SHT P-301 #'S 24, 25, 26 FUNNEL |
| | FLOOR DRAIN NOT APPROVED, FLOOR SINK RE- |
| | QUIRED FOR INDIRECT WASTE. SEC 802.3 |
| | 13) ROUTE PLANS THROUGH DEPT OF BUSINESS |
| | HOTEL AND RESTURANT DIVISION FOR PLAN RE |
| | VIEW BEFORE RESUBMITTING FOR CONST PLAN |
| | REVIEW. |
| | 14) PROVIDE CALCULATIONS FOR MINIMUM |
| | FACILITIES PER FBC-2001 PLUMBING TABLE |
| | 403.1 AND SEC 403. |
| | 15) SHT P-302 ITEMS #82/115 FILTERS, NSF |
| | APPROVAL REQUIRED. SUBMIT MANUF. INFO. |
| | 16) SHT P-302 ITEM #84 ICE MACHINE W/BIN |
| | NOT FOUND. |
| | 17) SHT P-302 ITEM #105 PLEASE CALL OUT |
| | 2ND DRAIN BOARD. |
| | 18) SHT P-302 ITEMS #134 & 136 NOT FOUND |
| | 19) PLEASE SUBMIT A SANITARY RISER DIA- |
| | GRAM WITH ALL THE PIPE SIZES AND SHOW |
| | FIXTURE UNITS AS THEY ACCUMULATE IN SYS- |
| | TEM. |
| | 20) SHT P-401 ROOM G-20 FLOOR DRAIN NOT |
| | SHOWN ON SANT RISER DIAGRAM. |
| | 21) SHT P-401 ROOM G-17 MENS FLOOR DRAIN |
| | NOT SHOWN ON SANT RISER DIAGRAM. |
| | 22) SHT P-401 MECH ROOM FLOOR DRAIN NOT |
| | SHOWN ON SANT RISER DIAGRAM. NOT FOR CON |
| | 23) SHT P-401 2" WASTE UP BETWEEN ROOM |
| | 2-E11 & #1 ELEVATOR NOT SHOWN ON SANT. |
| | RISER DIAGRAM. |
| | 24) SHT P-402 KITCHEN EQUIP PLMG SCHED. |
| | SHOWS 1 FRYER, GAS RISER SHOWS 2. ?? |
| | 25) SHT P-402 WATER RISER DIAGRAM, ALL |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| | AT TOP OF DROP AS SHOWN ON PLANS. LOCATE |
| | PER MANUFACTURE INSTALLATION INSTRUCTION |
| | AND PDI-WH 201. |
| | 26) SHT P-403, SHOW PIPE SIZES FOR ALL |
| | PIPING TO AREA DRAINS. SHOW SQUARE FOOT- |
| | AGE FOR ALL AREA DRAINS IN SYSTEM. COND. |
| | TO RUN SEPARATELY OUT OF BLDG AND TIE |
| | INTO STORM OUTSIDE. SUBMIT CONDENSATE |
| | RISER, SHOW RELIEF VENT AS COND. EXITS |
| | BLDG. |
| | 27) SHT P-403 STORM RISER DIAGRAM, PLEA- |
| | SE PROVIDE SQ FT OF GUTTER DRAINS ADDED |
| | TO ROOF DRAINS. |
| | 28) SHT P-403 STORM RISER DIAGRAM, UN- |
| | DERGROUND PIPE AT COLS 14-B/C SHOWS 6", |
| | THEN 8". PLEASE CLAIRFY |
| | 29) FOLLOWING INFORMATION REQUIRED FOR |
| | GAS PERMIT APPLICATION. |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | GAS CODE. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE. |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS CODE IF NATURAL |
| | GAS SPECIFY .5 PSI OR 2 PSI. |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2001 |
| | FUEL GAS CODE. |
| | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 30) SHT A-206 FAMILY TOILETS G-14, G-31, |
| | AND DETAIL #12. SHOW CLEAR FLOOR SPACE |
| | FOR HDCP FIXTURES. DOOR SWING SHALL NOT |
| | OPEN INTO CLEAR FLOOR SPACE OR UNOBSTRUC |
| | TED TURNING RADIUS. SHOW ON DETAIL. |
| | 31.SHT A-209 DETAIL #8 SHOWS 4 W/C'S |
| | WEST OF HDCP STALL, DETAIL #3 SHOWS 3 |
| | W/C'SWEST OF HDCP STALL AND 1 EAST IN |
| | WOMENS TOILET. PLEASE CLAIRFY. ALSO GIVE |
| | DIMENSIONS FOR 2ND HDCP STALL WITH GRAB |
| | BARS IN IT. |
| | 32) SHT A-210 DETAIL #11 LAV CAN NOT BE |
| | ON WALL OPPOSITE OF W/C IN UNISEX TOILET |
| | 66" CLEAR FLOOR SPACE REQUIRED FIG. 28 |
| | 33) SHT A-210 DETAILS #1, 5, 8 SHOW |
| | CLEAR FLOOR SPACE FOR HDCP FIXTURES. |
| | DOOR CAN NOT OPEN INTO CLEAR FLOOR SPACE |
| | FOR FIXTURES. ROOMS #3-020, 3-021, AND |
| | 3-009. |
| | 34) SHT A-210 DETAIL #9 SOUTH ELEVATION, |
| | LAV NOT SHOWN. |
| | 35) SHT A-209 DETAILS #4 & 5 SHOW CONT- |
| | ROL AREA FOR SHOWER ON DETAILS. 4.21.5 |
| | 36) SHT A-209 DETAIL #1 MENS/WOMENS |
| | DRESSING ROOMS - BENCH REQUIRED SEC |
| | 4.35.4 |
| | 37) SHT A-210 DETAILS #6 & 7 SHOW CONT- |
| | ROL AREA FOR SHOWER ON DETAILS. 4.21.5 |
| | 38) SHTS A-106 & A-210 CEO TOILET SHALL |
| | BE ADAPTABLE PER SEC 4.1.3(11) PROVIDE |
| | DETAILS |
| | 39) SHT C-8 SEE ATTACHED SHEET FOR APP- |
| | ROVED GREASE TRAP DETAIL. CITY OF W.P.B |
| | UTILITY APPROVED. |
| | 40) WHERE DOES RAIN WATER FROM CANOPY |
| | DRAIN TO? |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |