| 2002-03-26 00:00:00 | 1) CONSTRUCTION FENCE SHOWN ON SITE PLAN |
| | G-02 MUST NOT INTERFERE WITH ANY |
| | EXISTING EXITING FACILITIES OR ANY |
| | FIRE PROTECTION EQUIPMENT OR DEVICES. |
| | 2) PLEASE PROVIDE EXISTING FIRE HYDRANT |
| | LOCATIONS ON SITE PLAN. |
| | 3) NEW CONSTRUCTION MUST NOT INTERFERE |
| | WITH FIRE RESCUE ACCESS TO THE |
| | EXISTING BUILDINGS LOCATED ON THE SITE. |
| | 4) PRIOR TO STARTING CONSTRUCTION A |
| | SITE INSPECTION IS TO BE PERFORMED BY |
| | FIRE RESCUE TO ENSURE THAT TEMPORARY |
| | BARRIERS, ETC., DO NOT INTERFERE WITH |
| | ANY EXITING. |
| | 5) TEMPORARY BARRIER AT EXISTING STAIR |
| | # 4 TO BE NON-COMBUSTIBLE. |
| | 6) THE REMOVAL OF ANY COVERED WALKS OR |
| | PAVERS ARE NOT TO CREATE ANY HAZARDS TO |
| | PERSONS UNSING THE EXISTING BUILDINGS. |
| | 7) IT APPEARS THAT FIRE DEPT. VALVE |
| | BOX IN BLOCKED BY PARKING SPACE # 8 ON |
| | LEVEL 1-PARKING. |
| | 8) THE SAME CONDITION APPEARS TO EXIST |
| | FOR FIRE DEPT. VALVE BY PARKING SPACE |
| | # 12 ON LEVEL 2-PARKING. |
| | 9) STAIR # 1 AND STAIR # 3 SHOULD BE |
| | EQUIPPED WITH FIRE DEPT. VALVES. STAIRS |
| | # 1 AND STAIR # 3 PROVIDE COVERAGE FOR |
| | OTHER PARTS OF THE BUILDING. |
| | 10) PANIC HARDWARE REQUIRED ON ALL EXIT |
| | DOORS SUBJECT TO AN OCCUPANCY OF 100 |
| | OR MORE PERSONS. |
| | 11) ADDITIONAL EXIT SIGNS NEEDED TO |
| | DESIGNATE SECOND MEANS OF EGRESS FROM |
| | BANQUET ROOMS LOCATED ON THE GROUND |
| | LEVEL. |
| | 12) PLEASE INDICATE OCCUPANT LOADS FOR |
| | ASSEMBLY ROOMS LOCATED ON THE SECOND |
| | LEVEL. |
| | 13) PLEASE EXPLAIN RATIONALE FOR SINGLE |
| | EXIT ARRANGEMENT FOR OFFICE AREA NEAR |
| | PROG OFFICE 3-PO3. |
| | 14) PLEASE VERIFY THAT EXIT DOOR SWING |
| | IS CORRECT IN RECEPTION, WAITING 3-XO1. |
| | 15) IDENTIFICATION SIGNS REQUIRED FOR |
| | THE STAIR TOWERS. |
| | 16) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION INFORMATION FOR WALLS |
| | AND CEILINGS. |
| | 17) PLEASE EXPLAIN THE FOLLOWING NOTE |
| | " 50LB PICK UP POINT 1/4 X 1 DIA EYE |
| | BOLTS AT EVERY CROSSING (168 TOTAL) |
| | RECESSED INTO SPRINKLER HEAD |
| | ESCUTCHEONS WITH COVER" ON PAGE A-307. |
| | 18) BUILDING ADDRESS REQUIRED. |
| | 19) GUARDS ARE REQUIRED TO PREVENT A |
| | SPHERE OF FOUR INCHES TO PASS THROUGH |
| | THEM. |
| | 20) ARCHITECTURAL PLANS SHOULD INDICATE |
| | THE NUMBER OF AIR CHANGES AND THE CFM |
| | OF EXHAUST THAT WILL OCCUR IN THE |
| | UNDERGROUND PARKING AREA. |
| | 21) ARE THE F1E ITEMS IN THE PARKING |
| | AREAS EMERGENCY LIGHTING EQUIPMENT. |
| | 22) PLEASE SEE NOTE # 4 ON ELECTRICAL |
| | PLAN REVIEW. |
| | 23) ROOF MANIFOLD(S) ARE REQUIRED. |
| | 24) PLEASE EXPLAIN DESIGN FOR WATER |
| | CURTAIN SHOWN ON PAGE FP-203. |
| | 25) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR HOOD, DUCT AND EXTINGUISHING SYSTEMS |
| | 26) SEPARATE PLANS AND PERMITS REQUIRED |
| | FOR FOR FIRE ALARM SYSTEM INSTALLATION. |
| | 27) ELEVATORS TO COMPLY WITH FLORIDA |
| | ELEVATOR CODE 61C-5. |
| | 28) PLEASE INDICATE ON PLANS SMOKE |
| | DETECTORS FOR ELEVATOR RECALL. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |