| 2002-03-14 00:00:00 | FAILED : |
| | 1. PLEASE PROVIDE STORM WATER |
| | CALCULATIONS SHOWING PRE-CONSTRUCTIONS |
| | VS POST-CONSTRUCTION DISCHARGE RATE FOR |
| | THE SITE. |
| | 2. PLEASE PROVIDE HYDRAULIC CALCULATIONS |
| | SHOWING THE REQUIRED RCP SIZES. |
| | 3. PLEASE SHOW ALL THE EXISTING FIRE HYD |
| | ON SITE/NEARBY, ADDITIONAL FIRE HYD MAY |
| | BE REQUIRED. |
| | 4. PLEASE VERIFY, IF CONSTRUCTIONS OF |
| | 18" RCPS FROM S-8 TO S-9 AND TO S-10 AS |
| | SHOWN WOULD BE IN CONFLICT WITH |
| | CONSTRUCTION OF AUGER CAST PILES AND THE |
| | PROPOSED BUILDING'S FOUNDATION. |
| | 5. PLEASE SHOW CONNECTION FOR DOMESTIC |
| | WATER. |
| | 6. PLEASE SHOW CONNECTION FOR THE |
| | PROPOSED OIL/WATER SEPARATOR. |
| | 7. CONTRACTOR MUST CALL RODNEY COMPO, |
| | 837-4051 EXT. 4074 FOR APPROVAL, |
| | INSPECTIONS OF BOTH GREASE/WATER, OIL/ |
| | WATER SEPARATOR. |
| | 8. ANY WORK WITHIN PUBLIC R.O.W WILL |
| | REQUIRE A SEPARATE PERMIT FROM THE CITY |
| | ENGINEER'S OFFICE, 659-8040. |
| | 9. A SEPARATE PERMIT APPLICATION AND |
| | FEES FOR UNDERGROUND /SITE WORKS WILL BE |
| | REQUIRED AT THE TIME OF ACTUAL |
| | PERMITTING. |
| | IF ANY QUESTIONS PLEASE CONTACT 659-8096 |
| | EXT. 8492 MOHAMMAD R. AMINI |