| 2002-03-26 00:00:00 | ****************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE CLARIFY LIGHTING FOR |
| | FOOD STORAGE M-20 ON PAGE E-204. |
| | |
| | 2)NOTE: PLEASE NOTE THAT ALL CONTINUOUS |
| | LOADS (LIGHTING) ETC ARE TO BE FIGURED |
| | AND SHOWN AT 125%. 215-2/215-3 /230-42.. |
| | .... |
| | |
| | 3)NOTE: PLEASE CLARIFY PANEL SCHEDULE |
| | FOR EP4P2. SHOWS SF 1P- SF 6P? PLEASE |
| | CLARIFY WHAT THESE LOADS ARE? |
| | |
| | 4)NOTE: PLEASE CLARIFY GROUPING OF MAINS |
| | FOR EMERGENCY POWER. PLEASE NOTE MAIN |
| | ELECTRICAL COMING FROM ORIG BLDG AND |
| | GENERATOR POWER COMING FROM NEW BLDG |
| | OUTSIDE AND UP A LEVEL. PLEASE SEE |
| | FIRE PLAN REVIEW COMMENTS FOR THIS. |
| | PLEASE NOTE CONCERNS OVER SHUTTING MAIN |
| | OFF AND HAVINGGENERATOR START UP AND |
| | STILL FEEDING POWER INTO NEW BLDG. |
| | PLEASE NOTE FIREDEPT CONCERNS OVER |
| | THE DISTANCE OF TRAVEL FOR SHUTTING OF |
| | EM POWER IN 2-LEVEL GARAGE, THEN MCB |
| | ON THE INSIDE OF GENERATOR, (IF OUTSIDE) |
| | PLEASE SEE 230-72 FOR GROUPING OF MAINS, |
| | AND 230-76/230-79 FOR RATING OF MAINS |
| | FOR ELEC POWER. |
| | |
| | 5)NOTE: PLEASE SHOW LOAD CALCULATIONS |
| | FOR ADDING NEW SERVICE LOAD TO EXISTING |
| | SERVICE. |
| | |
| | 6)NOTE: PLEASE SUBMIT ALL PANEL SCHEDULE |
| | S, SCDP2? PLEASE CHECK FOR ANY OTHERS. |
| | |
| | 7)NOTE: PLEASE CLARIFY GROUNDING ATTACH- |
| | MENT FOR TRANSFORMERS.250-30 |
| | |
| | PLEASE SEE FIRE REVIEW COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |