| 2002-04-12 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | FBC = FLORIDA BUILDING CODE 2001 |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT WILL BE REQUIRED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) FBC* 104.2.4SITE SURVEY.A SIGNED |
| | AND SEALED SURVEY DRAWING PREPARED BY A |
| | QUALIFIED SURVEYOR IS REQUIRED. |
| | |
| | 4) FBC* 104.2.1.1ROOF COVERING PRODUCT |
| | APPROVAL SHALL BE SUBMITTED FOR THE ROOF |
| | COVERING SYSTEM TO BE USED (FBC 1504.3). |
| | |
| | 5) FBC* 1804.2.2SUBMIT A GEOTECHNICAL |
| | REPORT. |
| | |
| | 6) INFORMATIVE: |
| | FBC* 104.4.5 SPECIAL FOUNDATION PERMIT |
| | THE BUILDING OFFICIAL MAY, AT HIS |
| | DISCRETION, ISSUE A SPECIAL PERMIT |
| | FOR THE FOUNDATION ONLY, UPON WRITTEN |
| | REQUEST BY THE OWNER AND CONTRACTOR. THE |
| | HOLDER OF SUCH SPECIAL PERMIT IS PROCEED |
| | ING AT HIS/HER OWN RISK AND WITHOUT |
| | ASSURANCE THAT A PERMIT FOR THE |
| | REMAINDER OF THE WORK WILL BE GRANTED |
| | AND THAT CORRECTIONS WILL NOT BE |
| | REQUIRED IN ORDER TO MEET THE PROVISIONS |
| | OF THE TECHNICAL CODES. |
| | |
| | 7) FBC 1606.1.4WINDOW AND DOOR PRODUCT |
| | APPROVALS.SUBMIT PRODUCT APPROVALS FOR |
| | THE EXTERIOR DOOR AND WINDOW SYSTEMS TO |
| | BE USED. |
| | |
| | 8) FBC 11-4.1.2ACCESSIBILITY TO THE |
| | EXISTING KRAVIS CENTER BUILDING SHALL BE |
| | MAINTAINED THROUGHOUT THE CONSTRUCTION. |
| | |
| | 9) FBC 13-103COMPLIANCE SHALL BE |
| | DEMONSTRATED BY SUBMITTAL OF APPROPRIATE |
| | ENERGY CODE COMPLIANCE FORMS. |
| | |
| | 10) FBC 1003.3EGRESS CAPACITY OF |
| | STAIRWAYS.SHEET LS-105 'FLOOR AREA/ |
| | OCCUPANCY CALCS'.THE CALCULATED |
| | COMBINED STAIRWAY WIDTH REQUIRED IS |
| | 275.1".WHILST SHEETS A-201 TO A-204 DO |
| | NOT GIVE DIMENSIONS FOR THE FLIGHT WIDTH |
| | IT WOULD APPEAR THAT THE FOUR STAIRWAYS |
| | DO NOT HAVE THE REQUIRED COMBINED EXIT |
| | WIDTH.ADD DIMENSIONS TO SHOW THE WIDTH |
| | OF EACH FLIGHT AND AMEND/JUSTIFY THE |
| | STAIRWAYS FOR THE REQUIRED EXIT CAPACITY |
| | |
| | 11) FBC 1019.1.1EXIT FROM ASSEMBLY RMS |
| | SHEET LS-105, SECOND FLOOR.AS THIS IS |
| | NOT THE LEVEL OF EXIT DISCHARGE, EACH OF |
| | THE ASSEMBLY OCCUPANCY ROOMS SHALL BE |
| | PROVIDED WITH A MAIN ENTRANCE/EXIT THAT |
| | CONNECTS TO A STAIRWAY OR RAMP LEADING |
| | TO A STREET (AND CAN ACCOMMODATE 50% OF |
| | OF THE OCCUPANT LOAD).STAIR NO. 3 AND |
| | STAIR NO. 4 DISCHARGE , AT GROUND LEVEL, |
| | VIA A LOBBY AND LOADING DOCK |
| | RESPECTIVELY, NOT DIRECTLY TO A STREET |
| | OR OPEN SPACE LEADING TO A STREET. |
| | SHOW HOW THIS REQUIREMENT WILL BE MET. |
| | |
| | 12) FBC 1004.1.2EGRESS FROM 'PROJECTS' |
| | OFFICE SUITE. SHEET LS-105, SECOND FLOOR |
| | THE TRAVEL DISTANCE TO THE EXIT ACCESS |
| | DOOR FROM THE MOST REMOTE CORNER OF THE |
| | OFFICE EXCEEDS 75FT (APPROX. 88FT).ADD |
| | A SECOND EGRESS DOOR FROM THIS AREA. |
| | |
| | 13) FBC 1004.1.2EGRESS FROM 'PROGRAM.' |
| | OFFICE SUITE.SHEET LS-106, THIRD FLOOR |
| | THE TRAVEL DISTANCE TO THE EXIT ACCESS |
| | DOOR FROM THE MOST REMOTE CORNER OF THE |
| | OFFICE EXCEEDS 75FT (APPROX. 84FT).ADD |
| | A SECOND EGRESS DOOR FROM THIS AREA. |
| | |
| | 14) FBC 1004.1.4EGRESS FROM 'TRAINING |
| | SPACE/RECORDING STUDIO', SHEET LS-105. |
| | THIS SPACE CAN ACCOMMODATE MORE THAN 50 |
| | PEOPLE SO BOTH EXIT ACCESS DOORS ARE |
| | REQUIRED.THE TWO EXIT ACCESS DOORS |
| | CURRENTLY HAVE A SEPARATION OF 24FT |
| | WHICH IS LESS THAN THE MINIMUM REQUIRE- |
| | MENT OF 'HALF OF THE MAXIMUM OVERALL |
| | DIAGONAL (APPROX. 28FT).REPOSITION THE |
| | DOORS TO COMPLY. |
| | |
| | 15) FBC* 104.2.1.2THEATRE LAB A AND B, |
| | SHEET LS-105.AMEND THE PLANS TO |
| | DESCIBE THE OCCUPANCY OF THESE ROOMS. |
| | ARE THEY ASSEMBLY OCCUPANCY?IF THEY |
| | HAVE AN OCCUPANCY OF MORE THAN 50 PEOPLE |
| | THEN TWO EXIT ACCESS ARE REQUIRED |
| | (FBC 1004.1.2) AND THE DISTANCE BETWEEN |
| | THESE SHALL BE NO LESS THAN HALF THE |
| | MAXIMUM OVERALL DIAGONAL (FBC 1004.1.4). |
| | |
| | 16) FBC 1003.1 OCCUPANCY OF 'UNASSIGNED' |
| | ROOM, SHEET LS-106.THE OCCUPANCY FOR |
| | THIS ROOM SHALL BE SPECIFIED.IF IT IS |
| | STILL UNASSIGNED, THEN SPECIFY THE MOST |
| | HEAVILY OCCUPIED OF THE POTENTIAL USES. |
| | TO COMPLY WITH FBC 1012.12, OUTWARD |
| | OPENING DOORS MAY BE REQUIRED. |
| | |
| | 17) FBC 1012.1.2THE FOLLOWING DOORS |
| | SHALL BE REVERSED TO OPEN IN THE |
| | DIRECTION OF ESCAPE: |
| | -DOOR G26 (SHEET A-103) BETWEEN THE |
| | PREFUNCTION HALL AND SERVICE CORRIDOR |
| | -DOOR 253 (SHEET A-105) BETWEEN |
| | CORRIDORS 2-03 AND 2-02 |
| | -DOOR 340 (SHEET A-106) BETWEEN |
| | CORRIDORS 3-010 AND 3-001A |
| | |
| | 18) FBC 704.1PARKING GARAGE OCCUPANCY |
| | SEPARATION.THE AUTOMOBILE PARKING |
| | SHALL BE SEPARATED FROM THE LEVEL 1 |
| | ELECTRICAL AND ELEVATOR MACHINE ROOMS |
| | AND THE LEVEL 2 STORAGE, ELECTRICAL AND |
| | TEL/DATA ROOM BY ONE HOUR FIRE RESISTANT |
| | CONSTRUCTION, MINIMUM. |
| | |
| | 19) FBC 403.3PROJECTION ROOM.NORTH- |
| | SOUTH SECTION THROUGH BANQUETING HALL, |
| | SHEET A-411.CLARIFY THE USE OF THIS |
| | ROOM.IF CELLULOSE NITRATE FILM OR |
| | CELLULOSE ACETATE OR OTHER SAFETY FILM |
| | IS TO BE USED, COMPLIANCE WITH THIS |
| | REQUIREMENT MUST BE DEMONSTRATED. |
| | |
| | 20) FBC 2405.2IN ALL LOCATIONS WHERE |
| | GLAZING IS IN A 'HAZARDOUS LOCATION' IT |
| | SHALL BE SAFETY GLASS, SATISFYING THE |
| | REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).SUBMIT DETAILS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 21) FBC 104.2.1EXTERIOR ALUMINUM |
| | CLADDING PANELS.AMEND THE PLANS TO |
| | DESCRIBE THE ATTACHMENT OF THE ALUMINUM- |
| | FACED PLYWOOD TO THE BUILDING FACADE. |
| | |
| | 22) FBC 3003.4STRETCHER REQUIREMENTS |
| | FOR ELEVATORS.ANNOTATE THE PLANS TO |
| | DEMONSTRATE COMPLIANCE WITH THE |
| | REQUIREMENT FOR AT LEAST ONE PASSENGER |
| | ELEVATOR TO ACCOMMODATE AN AMBULANCE |
| | STRETCHER 76" LONG AND 24" WIDE IN THE |
| | HORIZONTAL POSITION.ALSO, THE ELEVATOR |
| | SHALL BE IDENTIFIABLE. |
| | |
| | 23) FBC 11-4.1.2(5)ACCESSIBLE PARKING. |
| | WITH A TOTAL OF 116 SPACES PROVIDED, AT |
| | LEAST 5 MUST BE ACCESSIBLE. SHEET LS-101 |
| | LEVEL 1 PARKING, DOES NOT SHOW ANY |
| | DESIGNATED ACCESSIBLE PARKING.THE |
| | 'ACCESSIBLE' PARKING SHOWN ON |
| | SHEET LS-102, LEVEL 2 PARKING, IS NOT |
| | COMPLIANT IN RESPECT OF AN ACCESSIBLE |
| | ROUTE (FBC 11-4.6.2(1)), AND WIDTH OF |
| | PARKING SPACE AND ACCESSIBLE AISLES |
| | (FBD 11-4.6.3).REF FIGURE 9A |
| | |
| | 24) FBC 11-4.8LEVEL 1 PARKING, |
| | SHEET LS-101.SHOW/ANNOTATE THE RAMP |
| | FROM PARKING LEVEL UP TO ELEVATOR LOBBY |
| | LEVEL FOR ACCESSIBILITY. |
| | |
| | 25) FBC 1015.3WALKWAY GUARDRAILS. |
| | SHEET A-708 SHOWS THE WALKWAY GUARDRAIL |
| | ON THE WEST ELEVATION (SHEET A-403) AS |
| | HAVING A RAIL SPACING OF 4" CLEAR.THIS |
| | WILL BE SUBJECT TO FIELD VERIFICATION BY |
| | THE INSPECTOR.NOTE THAT THE CURRENT |
| | PROPOSAL MAKES NO ALLOWANCE FOR |
| | CONSTRUCTION TOLERANCES, AS THE CODE |
| | REQUIREMENT IS FOR A MAXIMUM SPACING OF |
| | 4" CLEAR.THE POTENTIAL FOR CODE |
| | VIOLATION WILL BE HIGH IF THE SPACING IS |
| | NOT REDUCED TO ACCOUNT FOR CONSTRUCTION |
| | TOLERANCES.THE SAME COMMENT APPLIES TO |
| | THE 4" VERTICAL GAPS ON SHEET A-708, |
| | DETAIL 4. |
| | |
| | 26) FBC 11-4.8.5RAMP HANDRAILS.THE |
| | RAMP AT THE LOADING BAY DOCK SHALL BE |
| | PROVIDED WITH HANDRAILS THAT COMPLY WITH |
| | THIS REQUIREMENT IN ADDITION TO THE |
| | PROPOSED GUARDRAIL. |
| | |
| | 27) FBC 11-4.9.4(2)STAIRWAY HANDRAILS. |
| | SHEET A-810, DETAIL 6 RAIL AT WALL.THE |
| | LOWER HANDRAIL EXTENSION DIMENSIONS |
| | MARKED 'ONE TREAD' AND 1'-0" SHALL BE |
| | SWAPPED TO COMPLY WITH THE CODE |
| | REQUIREMENT. |
| | |
| | 28) FBC 11-4.1.3(5) ACCESSIBLE ELEVATORS |
| | THE PASSENGER ELEVATORS SHALL BE IN |
| | ACCORDANCE WITH FBC 11-4.10.ANNOTATE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 29) FBC 11-4.31PUBLIC TELEPHONES.THE |
| | CLEARANCES AND FACILITIES SHALL BE IN |
| | ACCORDANCE WITH THIS REQUIREMENT.AMEND |
| | THE PLANS TO DEMONSTRATE COMPLIANCE |
| | (REF. FIG 44) |
| | |
| | 30) FBC 11-4.15DRINKING FOUNTAINS. THE |
| | CLEARANCES AND SPOUT HEIGHT SHALL BE IN |
| | ACCORDANCE WITH THIS REQUIREMENT.AMEND |
| | THE PLANS TO DEMONSTRATE COMPLIANCE |
| | (REF. FIG 27) |
| | |
| | 31) FBC 11-4-19LAVATORIES.SUBMIT |
| | DETAILS TO SHOW COMPLIANCE WITH THE |
| | HEIGHT AND CLEARANCE REQUIREMENTS |
| | (FIGURES 31 AND 32) |
| | |
| | 32) FBC 11-4.16WATER CLOSET. |
| | SHEET A-208, DETAIL 11.THE HEIGHT OF |
| | THE TOILET SEAT SHALL BE 17" TO 19" |
| | ABOVE THE FLOOR.AMEND DETAIL 11 AND |
| | THE RELEVANT TOILET ELEVATIONS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 33) FBC 11.4.21SHOWER SEAT. |
| | SHEET A-208, DETAIL 10.THE SHOWER SEAT |
| | SHALL BE MOUNTED 17' TO 19' ABOVE THE |
| | BATHROOM FLOOR.THE HEIGHT SHOWN ON |
| | DETAIL 10 DOES NOT COMPLY, BUT THE |
| | HEIGHTS SHOWN ON SHEET A-209 DO COMPLY. |
| | AMEND SHEET A-208, DETAIL 10.ALSO, |
| | THE PLANS SHALL BE AMENDED TO SHOW THAT |
| | THE SHOWER CONTROLS AND SPRAY UNIT |
| | COMPLY WITH THE FBC 11-4.21.5 AND 4.21.6 |
| | |
| | 34) FBC 11-4.35DRESSING ROOMS, |
| | SHEET A-105.THE MEN'S AND WOMEN'S |
| | DRESSING ROOMS SHALL BE ACCESSIBLE, |
| | INCLUDING THE PROVISION OF BENCHES. |
| | AMEND THE PLANS TO DEMONSTRATE |
| | COMPLIANCE. |
| | |
| | 35) FBC 403.1.4.1BARS.TO COMPLY WITH |
| | FBC 11-4.5.2 THE NEW BARS SHALL EACH |
| | INCORPORATE A PORTION AT LEAST 60" LONG |
| | WHICH IS AT A HEIGHT OF 28" TO 34" ABOVE |
| | THE FINISH FLOOR WITH KNEE CLEARANCES IN |
| | ACCORDANCE WITH FBC 11-4.32.3. |
| | ALTERNATIVELY, SERVICE MUST BE MADE |
| | AVAILABLE AT ACCESSIBLE SEATING IN THE |
| | SAME AREA.AMEND THE PLANS TO |
| | DEMONSTRATE COMPLIANCE. |
| | |
| | 36) FBC* 104.2.1SHEET A-402, EAST AND |
| | SOUTH ELEVATIONS.AMEND THE KEY PLANS |
| | TO SHOW THE CORRECT VIEW DIRECTIONS. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |