Plan Review Notes
Plan Review Notes For Permit 02030677
Permit Number 02030677
Review Stop B
Sequence Number 2
Notes
Date Text
2002-04-18 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) FBC* 104.2.1SUBMIT A FLOOR PLAN TO
 SHOW THE OCCUPATION/USE OF THE NEW
 ROOM(S) AND THE MEANS OF ACCESS/EGRESS.
 IF IT IS TO INCORPORATE A SLEEPING ROOM,
 THEN THAT ROOM SHALL HAVE A DOOR OR
 WINDOW WHICH COMPLIES WITH THE EMERGENCY
 EGRESS REQUIREMENTS (FBC 1005.4.1).THE
 PLAN SHALL STATE THE FLOOR AREA OF THE
 NEW ROOM.
  
 3) NO ELECTRICAL, MECHANICAL OR PLUMBING
 PLANS HAVE BEEN SUBMITTED.SEPARATE
 PERMIT APPLICATIONS WILL BE REQUIRED FOR
 WORK UNDER THESE TRADES.
  
 4) FBC 13-103.0ENERGY CODE COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
  
 5) FBC* 104.2.1SUBMIT AN EAVES DETAIL
 SHOWING THE TYPE OF COVERING ON THE
 EXISTING ROOF, ROOF INSULATION, WALL
 INSULATION, CEILING AND WALL LININGS,
 AND EXTERIOR WALL SHEATHING AND WEATHER-
 PROOFING.
  
 6) FBC* 104.2.1STATE THE SIZE OF THE
 NEW WINDOWS.THE STATED DOOR HEIGHT OF
 6 FEET ROUGH IS INSUFFICIENT.
  
 7) FBC 1606.1.4WINDOW PRODUCT APPROVAL
 THE NOTICE OF ACCEPTANCE FOR THE 'SERIES
 PA-14 ALUMINUM SINGLE HUNG WINDOW' IS
 MISSING SHEET 2, WHICH SHOULD BE
 ENTITLED "....SPECIFIC CONDITIONS".
 ALSO, THE NOTICE OF ACCEPTANCE AND
 ASSOCIATED DRAWINGS ARE NOT FULLY
 LEGIBLE AS THEY HAVE BEEN REPEATEDLY
 FAXED/COPIED.SUBMIT COMPLETE AND
 LEGIBLE COPIES OF THE PRODUCT APPROVAL.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 REQUIRED HURRICANE MISSILE IMPACT
 PROTECTION SHUTTERS, OR A SEPARATE
 SHUTTER PERMIT APPLICATION WILL BE
 REQUIRED.
  
 9) FBC 2303.3WEATHER PROTECTION.THE
 STRUCTURAL FRAME AND INTERIOR WALL
 COVERING SHALL BE PROTECTED BY TYPE 15
 FELT OR KRAFT WATERPROOF BUILDING PAPER
 OR OTHER APPROVED WEATHER BARRIER.THE
 APPLICATION OF THE WEATHER PROTECTION
 BARRIER SHALL BE IN ACCORDANCE WITH THE
 CODE REQUIREMENT.
  
 10) FBC 2308.2.2.1THE EXTERIOR STUD
 WALLS SHALL INCORPORATE SHEATHING OF
 EXTERIOR GRADE PLYWOOD (MIN. 5/8" THICK)
 OR OTHER SHEATHING TYPE AS REFERENCED IN
 FBC TABLE 2308.2.2B
  
 11) FBC 2308.3.2 WINDOW AND DOOR HEADERS
 THE ENDS OF EACH HEADER SHALL BE
 SUPPORTED BY JACK STUDS AS SHOWN ON THE
 ATTACHED FIGURE.
  
 12) FBC* 104.2.1SPECIFY THE
 MANUFACTURER'S TYPE REFERENCE AND
 SPACING OF ANCHORS AND CONNECTORS FOR
 THE STUD WALLS.
  
 NOTE:
 AS PER LUIS MARTINEZ, THE ABOVE COMMENTS
 SUPERCEDE THE BUILDING PLAN REVIEW DATED
 4/4/02.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499