| Plan Review Notes For Permit 02030614 |
| Permit Number |
02030614 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-04-02 00:00:00 | ***************** FAILED *************** | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3} ALL BEDROOMS TO BE PROTECTED BY | | | A.F.C.I. PER 210-12. | | | | | | 4} KITCHEN ISLAND RECEPTACLES PER | | | 210-8(A)(6). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096EXT.8392 |
|